Technical information

FEEDER AND BRANCH CIRCUITS
25
2.6 Components accepted with restrictions
The UL 508A standard allows “Industrial Control Equipment” called “Manual Motor
Controllers” certified and marked as “Suitable as Motor Disconnect” as UL 508
switch device.
These switches should generally be protected by fuses against over currents.This
protection however may be provided in the field.
In the machine documentation the installation of an overcurrent protection, fuses
or boxed circuit breaker should however be explicitly required by the final user.
The manufacturer of the machine should indicate both the type and size of the
protection (calculated as per the following paragraph) and the cross-section of the
power conductors of the panel to be installed in the field (see example of wiring
diagram).
194E switch
prot. 23 +8 + 4 <= 35 A
RESPONSIBILITY OF THE FINAL
USER
AWG 8 (50A)
Sect. (1.15x22) + 8 + 4 >=37.3 A
Cond. 1.25 x 22 + 1.25 x 8 + 4 > = 41.5 A
AWG 8 (50A)