Technical information

FEEDER AND BRANCH CIRCUITS
27
EXAMPLE
As in the previous example a feeder protection and switch with circuit breaker
(series 140U) is taken up again.
The switching function requires a size of no less than 40 A but the calculation of
the value a) as overcurrent protection requires the size not to be more than:
22 + 8 + 4 = 34 A
The incompatibility of the design data is clear
Three solutions are proposed
1. Foregoing the protection function and sizing the 140U only as a switch. In
this case it will be necessary to install another device with a size no greater
than 35A to perform the function of the protection;
2.
Modifying the equipment to raise value a) from 35 to a value greater than 40 A
Prot 22 + 8+ 4 <= 34 A
Sect. 1.25 x (22 + 8 + 4) >=42.5 A
Cond. 1.25 x 22 + 1.25 x 8 + 4 > = 41.5 A
AWG 8 (50A)
Prot 35 + 8+ 4 <= 47A
Sect. 1.25x (22 + 8 + 4) >=42.5 A
Cond. 1.25 x 22 + 1.25 x 8 + 4 > = 41.5 A
AWG 8 (50A)