Technical information

The same calculation must be applied if the data is required for power
conductors of the machine and relative connection power blocks.
4.3 Reduction of the sections down line from the feeder
conductors
Once the feeder conductor has been cleared, it is also possible to define the
branches with a smaller cross-section called like “tap conductors”.
The rules regarding these conducts are only contained in the NEC and the CEC
and are very similar.The tap conductors are divided on the basis of length:
a) taps (cab les) less than 3 m (10 ft) long: all the conditions imposed should be
respected: the capacity of the conductor should always be adjusted to the
load powered (for example if the load is a motor,the derivation should have a
capacity of at least 125% of its FLA).
FEEDER AND BRANCH CIRCUITS
32
Cond. 1.25 x 22 + 1.25 x 8 + 4 > = 41.5 A
www.infoPLC.net