Technical information

FEEDER AND BRANCH CIRCUITS
33
•the tap should not extend further than the BCP of the powered loads
•to guarantee the mechanical protection, the derivation should always be
enclosed in conduits or raceways (not walk over covers) the connection
points obviously excluded.The CEC furthermore requires the conductors to
be metallic.
Furthermore the NEC provides:
•if the tap leaves the panel it shall have a capacity of not less than 1/10 of
the size of the feeder protection
b) t
aps (cab les) of a length no more than 7.5 m (25 ft.): all the conditions set
should be respected:
•the size of the conductor should always be adjusted to the powered load
•the capacity of the conductor should not be less than 1/3 the size of the
feeder protection
•each tap should feed a single BCP (there is no limit to the number of loads
downstream from the BCP provided the relative conductors are protected
by the BCP on the basis of the rules already seen)
•mechanical protection should be guaranteed.The use of conduits or
raceways (not walk over covers) is recommended.
Maximum 10 ft (3.05 meters)
www.infoPLC.net