Technical information

The sizing of the disconnecting means for a motor starter depends on how many
motors are sectioned and the type of sectioning used:
a) single motor, disconnecting device defined in curr ent: the rated current of the
disconnecting means must not be less than 115% the current of the motor;
b) single motor, disconnecting device defined in hp (pow er): for NEC and CEC it
is enough that the size of the disconnecting means in hp is greater than the
power of the motor,while UL508A requires to establish the current on the
basis of tables 50.1 and 50.2 and then apply the 115% rule described in the
previous point;
It is recommended that you follow this criterion for simplicity' sake.
c) mor e than one motor: refer to the case of a single motor with current equal to
the sum of all the motor currents (as usual the FLA for the USA and value of the
motor plate for Canada).The sizing is done in current by applying the lower
limit of 115%: in the case of the disconnecting means defined in hp (power)
the value obtained from tables 50.1 and 50.2 must be taken as rated current.
Note that a self protected combination motor starter type E cannot section
multiple motors.
EXAMPLE
The disconnecting means chosen must have power sizes not lower than 5 hp.
The suitable IEC/UL/CSA component is a 194E-25 disconnect switch with a
rating of 5 hp.
In a NEMA starter a 1494F-N30
able to section 7.5 hp will be
used: if the installation is directly
on the machine a 1494F-NP30
“enclosed” disconnect can be
used.
1.3.1.3 Overload protection
193-E UL 592 NEMA
BRANCH CIRCUIT
47
www.infoPLC.net