Technical information

The thermal protection is required f or all the motors r egardless of the size, unless
the motor is marked and authorised as self protected (impedance of the windings
is sufficient to prevent overloads).
Thermal relays, fuses, all the overload relays are admitted as protection from the
overload.
The power converters e.g. the reverse devices can perform this function only if
explicitly indicated in the instructions and only if the related instructions comply
with to the letter: some converters check the overload internally make checking
the through energy (I
2
t), other converters require the use of thermostats or
thermocouples. Failure to comply with the instructions will mean the protection
function is nullified.
The motors can have integrated protection providing that the assembly is certified
in all its parts: the use of self-protected must be shown in the schematics.
The maximum protection calibr
ation m ust not e xceed 115% of the r ated curr ent on
the plate. In the case of slow intervention, on start up or during normal
functioning, the protection can be increased up to 130%: in the case of components
that can be regulated the correct calibration must be indicated on the schematics.
In the case of thermal relays with resistors that can be replaced (NEMA
construction relays) the proper calibration must be shown on the schematics and
the catalogue code of the element be replaced must be attached.
EXAMPLE
In the example the plate current
is suggested and if it is unknown
FLA figures are used.
The calibration must not be
greater than 7.6 A x 1.15 = 8.7 A
If an overload relays with an
adjustable threshold is used the
device 140M-C2E-C10 with
adjustability range between
6.3 A and 10 A will be selected.
If a IEC/UL/CSA thermal relays
is used the choice will fall on
the 193-ED1DB (electronic)
with regulation range between
3.2 and 16 A.
At the moment of installation
the overload relays and
electronic O/L relays must be
adjusted at 100% of motor FLA.
BRANCH CIRCUIT
48
(*) Effective March 1, 2007 internal wiring < 14 AWG is only permitted in
industrial machinery panels, and must be protected by a device marked
suitable for connection and protection of that gauge of wire.
(*)
www.infoPLC.net