Technical information

The protection device must have size/regulation that does not exceed the
product “current x coefficient”, but if the value calculated does not coincide with
a standard size/regulation, the use of the one immediately above is acceptable.
Take for example a 10 A motor: using rapid fuses (nontime-delay) the coefficient
is 300% and the product is equal to 10 A x 300% = 30 A, standard size.On the
contrary when (time-delay o dual element) delayed fuses are used, the
coefficient is 175% and the product equals 17.5 A that is not the standard size: in
this case fuses up to 20 A can be used.
If the values indicated in the table are not sufficient to guarantee the start up of
the motor without the slow intervention of the protection, the tabulated values
can be used up to:
•fuses without delay or CC class up to 600 A: 400%
•fuses without delay over 601 A: 300%
•(dual element delayed fuse: 225%
•automatic thermomagnetic cutout not above 100 A: 400%
•automatic thermomagnetic cutout not above 100 A: 300%
•magnetic cutout for Design B, C or D motors: 1300%
•magnetic cutout for Design E motors: 1700%
Use of instantaneous trip (magnetic only) breakers must be part of a listed
combination of MCP + Contactor + O/L Relay. Alternatively, UL panel shops can have
combinations procedure described.
EXAMPLE
Furthermore it is assumed that the
restrictions of the contactor and the
thermal relay are negligible for the
purposes of choice and scaling of
the BCP.
a) Not-delayed fuses: the maximum
size is 7.6 A x 300% = 22,8 A that
is not the maximum standard for
which the use of fuses up to 25
A is legitimate. CC fuses (dim.
10x38) are chosen. The suitable
fuse holder is the 1492-FB3C30
or 140F-03C-C30.
b) automatic circuit breaker: the
maximum size is 7.6 A x 250% =
19 A that is not the standard size
so the use of a 20A circuit
breaker is legitimate.
The thermo magnetic for this
use is the 140U-H2C3-C20,with
an interrupting capacity of 35 kA
at 240 V.
BRANCH CIRCUIT
52
www.infoPLC.net