Technical information

c) Motor protector type E: the 140M-C2E-C10 previously chosen on the basis of
the thermal protection is kept.The additional use of fuses or magnetic only
circuit breakers is not required, provided the spacing adapter 140M-C-TE is
used (as is clearly indicated on the label).
1.4 Wye-delta starting
170 540
The wye-delta starters are dealt with special rules and tables and the UL508A in
particular dedicates an entire paragraph to it.
The reference schematic is:
1M line contactor
2M delta
Swye
On the basis of the functioning sequence the functioning conditions of the
individual contactors are specified:
1M “closed” when the motor is wye closed,“open” when the motor is running
to full capacity;
2M “closed” when the motor is being started,“open” when the motor is running
to full capacity;
S “closed” when the motor is closed,“open” when the motor is being started.
For each contactor it is possible to define a current value to be opened, called
“break current”, and a current value to be closed, called “make current”.
BRANCH CIRCUIT
53