Technical information

The choice of the contactors occurs as in a normal direct starting supposing that
each of them commands a dummy motor with current, at fully capacity and with
blocked rotor,equal to those calculated.
In the catalogue, the contactors are specified by power so it is necessary to
convert the calculated current values into power output (hp).The procedure is
opposed to that for obtaining the FLA: starting from the calculated current the
three-phase motor is sought that, at 480 V, has an FLA that is not lower.The
following is obtained
The fault for which the "wye" is larger than the line contactors and delta is
immediately clear: this is a direct consequence of the case for which the
switching occurs when the rotor is blocked.
EXAMPLE 2
The normal case is assumed with a start where the switching from wye to delta
occurs when the motor has already started at suff icient speed:
The same motor as in the previous example is assumed: 20 hp (15 kW) a 480 V
of which the rated current and the value of the current when the rotor is blocked
are unknown
From the table it is read that the FLA of the motor is 27 A and that LRA is 162 A
(that is 6 x 14 A). In this case the operating currents of the contactors are:
BRANCH CIRCUIT
55
Contactor code
FLA calculated Motor power Contactor
[A] FLA print out Power
1M 16
15 hp 100-C23
21 A15 hp
2M 16
15 hp 100-C23
21 A15 hp
S53
50 hp 100-C72
65 A50 hp
Contactor code LRA FLA
1M 0.33 x LRA motor 0.577 x LRA motor
2M 0.577 x LRA motor 0.577 x LRA motor
S00.33 x FLA motor
Contactor code LRA FLA
1M 0.33 x 162 A z 53 A0.577 x 27 A z 16 A
2M 0.577 x 162 A z 93 A0.577 x 27 A z 16 A
S00.33 x 27 A z 9 A
www.infoPLC.net