Technical information

The choice of the contactors occurs as in a normal direct starting supposing that
each of them commands a dummy motor with current, at full capacity and with
blocked rotor,equal to those calculated.
In the catalogue, the contactors are specified by power so it is necessary to
convert the calculated current values into power values (hp).The procedure is
opposed to that for obtaining the FLA: starting from the calculated current the
three-phase motor is sought that, at 480 V, has an FLA that is not lower.The
following is obtained
Of course the wye and delta contactors remain the same while the wye is now of
a smaller size.
Scaling in accordance to North American criteria as just shown, while following
precise tables defined in UL508A, brings us to make product choices identical to
the ones of the drawings done in accordance with European criteria.
EXAMPLE 3
The normal case is assumed with a start where the switching from wye to delta
occurs when the motor has already started at sufficient speed: It is furthermore
supposed that the motor is standard: LRA (block ed r otor curr ent\) = 6 x FLA (full
load curr ent).
On the basis of the hypothesis made it is not necessary to size the contactors on
the basis of the currents but reference may be made to table 33.3 of UL508A.This
table on the basis of the power and voltage of the motor defines the NEMA size of
the contactors to use: the NEMA size is a construction size that is shown in the
catalogue or on the component.
BRANCH CIRCUIT
56
Contactor code
FLA calculated Motor power Contactor
[A] FLA print out Power
1M 16
15 hp 100-C23
21 A15 hp
2M 16
15 hp 100-C23
21 A15 hp
S9
7.5 hp 100-C12
11 A7.5 hp