Technical information

The size/calibration of the protection of the branch circuit must not be more
than the low est v alue between the two following:
•the size of the BCP is established by calculating the size required for the
largest motor in the assembly (by doing this the product of the sizing
current of the largest motor by a coefficient in the table, has already been
seen for the individual motor start) plus the sum of the full load currents of
the remaining motors and the nominal currents of all the other loads in the
group; or
•the size of the BCP is chosen in such a way that all the power components
do not exceed the value of the current specified in the marking as regards
the group installation and the type of protection is the type specified in
the same marking (for this purposes,the term fuse refers to a branch
circuit protection connected with fuses and the term circuit breaker refers
o an automatic cutout at reverse type).
Finally it should be noted that the group installation can only be carried out
with automatic fuses and circuit breakers of the “inverse time” type: the
o v erload r elay of T ype E cannot be used as BCP f or a g r oup installation.
EXAMPLE
A calculation is required of the size/calibration of a branch circuit protection for
the following motor group installation: a 10 hp (7.5 kW) motor and two 5 hp
(3.5 kW) 480 V motors.The rating plate current is unknown
The FLA tables are: 14 A for the large motor,7.6 for the other motors.
The branch circuit protection consists of a delayed fuse: its coefficient for the
calculation of the BCP is 175%.
The protection size must be lower than:
14 x 1.75 Avalue calculated as for individual motor start
7.6 AFLA
7.6 AFLA
for a total of 29.7 A.The size of the fuse immediately below is 25 A.
In the previous calculation the restrictions imposed by the downstream
components have been ignored because generally larger sizes/calibrations are
acceptable.
If,on the other hand, the maximum protection allowed delayed fuses of 20 A, this
value would prevail over that calculated (25 A) and the fuses would have to be of
sizes no greater than the 20 A allowed.
The CEC allows a group installation in accordance with points a) and b), while it
limits the application of point c) to just machine tools and for wood working.The
CSA does not lay down specific restrictions for the group installation so the BCP
size limit is always obtained through calculation (the largest motor plus the other
loads); maximum values are imposed for the size of the branch circuit branch
circuit protection: 200 A up to 250 V, 100 A from 251 V up to 750 V.
BRANCH CIRCUIT
60
www.infoPLC.net