Technical information

The NFPA 79 standard for Industrial Machinery (and the relative UL508A
section) allows a group installation in accordance with points a) and b), but
point c) changes in the definition of the lowest value for the choice of the BCP:
the one linked to the markings remains the same while the other is no longer
obtained by a calculation but by a table (tab. 66.2 of UL508A) that binds the size
of the BCP to the conductor with the smallest cross section downstream of the
protection itself.
1.5.2 Sizing of conductors to the single motor.
In the case of group installation the circuit generally consists of conductors
(called branch circuits) leaving the BCP protection to arrive at a distribution
system (e.g. taps) from which the switching conductors powering the motors
leave again, normally with a lower cross-section.
The conductors of each tap that power a single motor do not need to have an
individual branch circuit protection from the short circuit provide the following
conditions are respected.
1) no conductor to the motor must have a lower capacity than the feeder
conductors capacity; or
2) no conductor to the motor must have a capacity lower than one third of that
of the i branch circuit conductors (with a minimum value not less than the
usual 125% of the motor current);the overload protection conductors must
be the same as or shorter than 7.62 m and protected manually.
3) the conductors that go from the branch circuit protection to a “manual
motor controller,” also approved as “Suitable for Tap Conductor Protection in
Group Installations”, can have a capacity of no less than 1/10 of the BCP
calibration (rule included in the NEC until 2002) and in the new NEC ed.
2005 can have a capacity not lower than the size calibration of the BCP
(fuse or motor protector).
4) The conductors from the controller to
the motor must have a capacity of no
less than the usual 125% of the motor
current.
The conductors from the BCP to the
controller must be adequately protected
mechanically, segregated and they must
be in lengths of not more than 3 m, or
they must have a capacity of not less than
that of the “branch circuit” conductors.
A particular case of group installation is represented by the “common bus” in
direct current: these systems consist of power rectifier that powers a short circuit
that in its turn powers one or more inverters (and relative motors downline).
The UL508A standard gives specific instructions for these components:
BRANCH CIRCUIT
61
140M
www.infoPLC.net