Technical information

•all the components in the system must be approved
•it is sufficient for there to be a single branch circuit protector up line from the
rectifier the size/calibration of which must be no larg er than the smallest v alue
of the following two:
a) the size required for the larger of the motors in the group plus the sum of
the full load currents of the remaining motors (in the same way as required
in point c) for the group installation); or
b) the maximum size allowed by the rectifier,in the instructions or in the
markings.
1.6 Three-phase, two-speed or Dahlander motor
The motors with multiple winding and those with Dahlander starting have
multiple power supply terminal strips, each characterised by its own current
characteristics. Every power entrance must be protected as if it were a single
motor on the basis of the rules defined above.
The only exception allowed is the use of a single protection from the BCP short-
circuit that however must be scaled in such a way as to meet the regulations for
all the windings connected downline.
1.7 Reversal of direction
The reversal of direction requires an interlock between the two contactors that
command the direction of turning.
The interlock can be mechanical or electrical, but there is an exception in the
case of Industrial Machinery: in the USA the NFPA 79 standard (and UL508A in
the relative section) require the use of both types of interlock.
1.8 VFD Inverter and Softstarter
Inverter and softstarter demand that the branch circuit protection, against short-
circuits, is made according to the indications of the instruction manual (as
established in the UL 508A § 31.3.2 ).
Without this datum, it is allowed to size the protection as if it were a motor by
multiplying the feed current of the drive, indicated in the manual, by the
coefficient indicated in the relevant tables.
BRANCH CIRCUIT
62
www.infoPLC.net