Technical information

Supply can be provided through:
•transformers with separate winding down line from the main disconnect of
the machine; the secondary must be protected;
•transformers with separate winding up line from the main disconnect of
the machine; the secondary must be sectioned;
•one 120 V control circuit with its own protection against over currents.
b) the CEC makes a difference between the maximum size/calibration of the
BCP on the basis of the power supply voltage:20 A for voltages up to 347
phases higher than 347 V, 15 A for higher voltages.
The command of a lighting circuit requires contactors that are specifically
approved for this purpose: the “lighting contactor”: The sizing must be done on
the basis of the current. One example of these contactors:
•100L series for the IEC/UL/CSA contactors: there is one size and it is 20 A;
•500L series for NEMA contactors: every size has a different current value, from
10 A to over 2000 A.
The maintenance lighting inside the panel is only dealt with in UL508A (as it is a
regulation specifically for panels) and, or Industrial Machinery, in NFPA 79
(because of the “origins” in IEC 60204-1).
a) UL508A:
•the lighting equipment must be approved in accordance to UL496 in the
CCN OMTT or ONHR, or in accordance to UL1570 in the CCN IEUZ.
•the voltage between conductors must be lower than 150 V.
the circuit must be considered as a power circuit and protected as already
defined. One exception is permitted: if the power supply occurs at 120 V and
it is derived downline from a control conformer with separate windings,
then the circuit can be considered as a control circuit and managed as such.
b) NFPA 79 (and relative section of UL508A):
•the lighting equipment must be approved (the previous UL approval classes
of course apply);
•less than 150 V; less than 15 A (as for all lighting circuits)
•in addition to the cases already described, the maintenance supply circuit
inside the panel can be derived from the secondary of a transformer with
separate windings upline of the machine's main disconnect (and must not
be sectioned or protected) or from the lighting circuit of the plant.
1.11 Appliance branch circuit
Any electrical user equipment mass produced to carry out a particular function is
called an appliance. In general they are non industr
ial devices (for example
household appliances).
Very often appliances are connected to a socket by means of a lead meaning that
for sizing the rules already seen for the receptacles are applied.
In cases where the ’appliance is directly connected it is necessary to provide for a
branch circuit, chosen with the following criteria (taken from UL508A):
BRANCH CIRCUIT
66
www.infoPLC.net