•the type and size of BCP indicated on the markings of the device; in the
absence of indications on the device, the following applies:
•if the appliance consists of at least one motor it must be protected as a motor
(or group of motors) with the same power output;
•if the ’appliance does not contain a motor it is necessary to verify the rated
current: if the current is less than 13.3 A the BCP must have a size that does not
exceed 20 A; if this is not the case the size/calibration of the BCP must be
smaller than 150% of the rated current.