Technical information

CONTROL CIRCUITS
73
The Class 1 circuit terminal block should be clearly indicated with a marking.
EXAMPLE
A control circuit made of AWG 18 cross section conductors is assumed.
If the interface terminal block accepts a AWG 18 AWG 14 cross-section interval,
one can go ahead regularly; if on the other hand the terminal block only accepts
sections AWG 18 AWG 16 then the maximum cross-section to be used should be
indicated, for example on the schematics.
1.3.4 Internal Wire
The conductors inside the panel follow the same rules given for power
conductors, except for the calculation of the section.
For the control circuits it is enough for the cable capacity not to be smaller than
the rating of the protection upline or in its absence to the nominal current to the
secondary of the control transformer.
F
or the capacities of the e xter
nal conductors it is advisab le to take tab le 28.1 of
UL508A as a r eference.
The operating temperature of the conductors is 90°C for wire size above AWG 16
and 60°C for conductors with cross sections the same as or lower than AWG 16
(it should be remembered however that a AWG 16 to 60°C conductor cannot be
used for power circuits).
The minim
um cross-section to be used for the internal control circuits is in both
te
xts A WG 18, but only wire size lower than AWG 30 are allowed for wiring for
PLC or static components (semi conductors and/or electronic). In UL508A table
38.1 shows the capacities allowed for conductors lower than AWG 18.
All the control circuit conductors inside the same raceway should be insulated for
the maximum voltage present if one of the conductors is not insulated for a lower
voltage,it is necessary to distance or isolate it.