Technical information

The North American standards require the protection of all the conductors that
are not connected to the equipotent circuit.
EXAMPLE
A general control circuit is
assumed to be derived of a
special branch circuit Q2
protection down line, for example
a circuit breaker (UL489) 140U-
H2C3-C15 of 15 A or 1489-A2C-
150,that protects a solenoid valve
assembly (Y1,Y2,Y3) and an
electronic component (U1).
From table 29.1 the protected
BCP cross-section, or AWG 14 (20
A) is obtained.
If the wiring is all made with
AWG 14 and no component
imposes particular restrictions,
the circuit represented is correct
and does not require anything
else.
It is now assumed that the U1 component imposes the use of a 4A protection, in
the marking, or in the instructions.
There are two solutions:
•to limit the entire circuit by
replacing the BCP Q2 15 A with
another of 4 A
•to insert a further Q3 4 A
supplementary protection that
protects just the conductor
supplying U1. For example a
1492-SP1C040, supplementary
protection (UL1077 approved)
can be used. Furthermore, down
line from the Q3 protection it is
possible to wire with a AWG 18
and 7A capacity conductor.
The first solution makes it possible to save a component, but limits the
possibilities of the control circuit.The second solution cuts in locally respecting
the requirements of component U1.
CONTROL CIRCUITS
76
www.infoPLC.net