Technical information

1.7.4 Internal Wiring
Approved conductors of Low-Voltage Limited Energy circuits should be separated
or isolated from conductors of the other circuits unless they are insulated f or the
maxim
um v oltag e present.
It should be noted that (as for Class 2 circuits) if internal non approved
conductors are used for example N07V-K or H05V-K, what has been said above is
no longer applicable and it is necessary to separate or isolate these conductors.
1.7.5 Circuits and components excluded from class 2 and
Low-voltage limited-energy circuits
Attention to the product:
–Safety devices like immaterial safety barriers, safety limit switches, sensitive
edges etc.
–motors & power loads, inverters, 24v step motors, etc.
Even if inserted and connected to power sources in class 2 and/or Low-
voltage limited Energy sources they should always be approved by an
NRTL laboratory.
1.8 Transformer and self transformer protection
NEC, CEC and UL508A do not really make distinctions between transformers and
self transformer,limiting themselves to preventing the use of the self transformer
in some civil systems.There is no limitation placed on its use for adapting the
input voltage to the electrical equipment panel.
Transformer protection follows in precise rules in the NEC and the CEC
r
egardless of whether the use is power or control, while the UL508A makes a few
distinctions.
The NEC and CEC are how e v er diff erent: the difference cannot be neglected
because it is often the cause of non conformities in Canada, where stricter rules
are applied.
CONTROL CIRCUITS