Technical information

The conductor to the secondary should carry at least 5 x 10 = 50 A.Table
29.1 of UL508A is used to select a AWG 8 (60 A), considerably greater than the
AWG 14 (20 A) that would have been sufficient considering the single current
to the secondary.
•pr
imary and secondary: the protection should be graded to values of no
more than
[a]
if the rating does not correspond with a standard value (see the publication
prior to section “BCP”) the one immediately above the one calculated is
permitted.
Standard UL508A limits itself to increasing the percentage for currents to
the primary below 2 A by imposing:
•Current transformers: 500%
•Power transformers: 300%
The protection of the secondary can be obtained with a special component
or with the sum of the ratings of the protections down line.
In the case of single phase control transformers with one side of the
secondary connected to the equipotent circuit, it is sufficient a single
protection positioned on the side not connected (exactly as in Europe).
The conductors to the primary and the secondary should have a capacity of
no less than the rating of the relative protection.
EXAMPLE
The same single phase transformer of 450 VA as the previous example is
considered.
primaryV
1N
= 240 VI
1N
= 1,88 A
secondaryV
2N
= 24 VI
2N
= 18,8 A
Let’s say it is protected on the primary and on the secondary.
CONTROL CIRCUITS
86
PrimarySecondary
Current Rating protection Current Rating protection
I1 [A] [percentage of I1] I2 [A] [percentage of I1]
9250 % 9125 %
[a]
< 9250 %<9167 %
< 2250 %