Technical information

The conductors to the primary and the secondary should have a capacity of
no less than the rating of the relative protection.
1.8.1 Protections Allowed
The protection should be made with suitable components at the point of
installation of the transformer/auto transformer.The most common can be
specified
•self transformer on input to the panel to adapt the v oltag e: as already
mentioned in the chapter on power circuits, the transformer is inserted inside
the feeder and should therefore be protected with:
–primary: fuses for the power circuits (for example CC or J fuses and relative
fuse holders 140F, 1492-FB) or molded case circuit breakers (e.g. 140-U);
–secondary: as for the primary unless the protection is the sum of the branch
circuit protections (BCP).
•control transformer pow ered b y the f eeder:
–primary: the protection of the transformer is for all intents and purposes a
BCP,but special components cannot be used for motor starting such as
combination motor controller or manual motor controller;
–secondary: we are inside the control circuit, thus all components can be used
including the supplementary protection (e.g. the miniature circuit breakers
1492-SP).
•the control transformer powered down line with an existing branch circuit
transformer: primary and secondary are already part of the control circuit thus
all the components can be used including the supplementary protection (e.g.
the miniature circuit breakers 1492-SP). The protection to the primary can be
omitted if the rating if the pre-existing BCP satisfies the sizing indicated above.
CONTROL CIRCUITS
88