Technical information

b) The short circuit current
rating determined by the
voltage rating of the
component and the assumed
short circuit current rating
from Table SB 4.1;
If the power circuit component
does not have a short circuit
current rating or has not been
required to have a rating in the
past,Table SB4.1 in UL508A,
Supplement SB lists the assumed
maximum short circuit current
rating for unmarked products.
c) The short circuit current rating for a load controller,motor overload relay, or
combination motor controller that has been investigated in accordance with
the performance requirements, including short circuit test requirements for
standard fault currents or high fault currents specified in the Standard for
Industrial Control Equipment, UL 508, and described in the manufacturer’s
procedure.
Part c) states that specific tested combination ratings can be used by a panel
manufacturer if the combination ratings are included their UL procedure file.
Rockwell Automation tests and certifies a wide-range of NEMA and IEC
components to meet the requirements of NEC Article 409 and UL 508A,
Supplement SB (See page 100).
INDUSTRIAL MACHINERY
96
Nameplate
Table SB4.1 Assumed maximum short circuit
current rating for unmarked components
Examples of short circuit current rating product markings on nameplates and in
reference documents