TROUBLESHOOTING FLOW CHARTS
NNOO
YYEESS
NNOO
YYEESS
NNOO
11
22
11
22
YYEESS
NNOO
YYEESS
NNOO
UNIT DOES NOT FUNCTION
NNOO
NNOO
11
22
11
22
YYEESS
NNOO
NNOO
YYEESS
UNIT IS CONTINUOUSLY FLUSHING
YYEESS
NNOO
NNOO
11
22
11
22
NNOO
YYEESS
UNIT WILL ONLY FLUSH MANUALLY
OPEN VALVE
LOW VOLTAGE. TEST OUTPUT OF
TRANSFORMER. MUST BE >5.4 VAC.
BAD TRANSFORMER. REPLACE. REPEAT.
BAD TRANSFORMER. REPLACE. REPEAT.
DAMAGED SENSOR. REPLACE
SENSOR.
DAMAGED SENSOR. REPLACE
SENSOR.
BAD TRANSFORMER. REPLACE. REPEAT.
DAMAGED SENSOR. REPLACE
SENSOR.
DAMAGED SOLENOID. REPLACE
SOLENOID
DAMAGED MANUAL OVERRIDE
BUTTON. REPLACE MANUAL
OVERRIDE BUTTON
CRITICALLY LOW BATETRY. INSTALL
NEW BATTERY
IS ANGLE STOP OPEN?
REPEATED DOUBLE
FLASH ON SENSOR?
RECONNECT TRANSFORMER TO
SENSOR. FLASH ON SENSOR FOR
5 SECONDS?
RECONNECT TRANSFORMER TO
SENSOR. FLASH ON SENSOR FOR
5 SECONDS?
RECONNECT TRANSFORMER TO
SENSOR. FLASH ON SENSOR FOR
5 SECONDS?
PUSH MANUAL OVERRIDE
BUTTON; WILL THE UNIT FLUSH?
REPLACE PISTON ASSEMBLY.
CLOSE ANGLE STOP AND OPEN
AGAIN TO PRIME THE VALVE.
DOES FLUSHING STOP?
PUSH MANUAL OVERRIDE
BUTTON. DOES IT RETURN TO ITS
ORIGINAL POSITION FREELY?
REPLACE PISTON & SOLENOID
ASSEMBLY.
REPEATED DOUBLE
FLASH ON SENSOR?
REPLACE SOLENOID.
HOT LINE FOR HELP
For toll-free information and answe
rs to your questions, call:
(844) CRT-TEAM / (844) 278-8326
IN CANADA 1-800-387-0369 (TORONTO 1-905-306-1093)
Weekdays 8:00 a.m. to 7:00 p.m. EST
IN MEXICO 01-800-839-1200
Pr oduct names liste d her ein are tr ade mar k s of AS A mer ica, Inc. ©2019
To learn more about American Standard Selectronic
®
Products visit our website at:
www.americanstandard-us.com or e-mail us at: CRTTEAM@lixilamericas.com
Mon.– Fri. 8:00 a.m. to 8:00 p.m. EST Sat. 10:00 a.m. to 4:00 p.m. EST
M965645 EN REV. 2.2 (10/19)