DIAGNOSTICS AND SERVICE (continued)
SPACE TEMP SENSOR FAILURE ( )
The Space Temp Sensor Failure fault will occur when the UVC detects
an open or a short condition from the space temperature sensor.
Effect:
Space fan is de-energized (unless in emergency heat mode)
Compressor is immediately de-energized
Outdoor fan (if present) is de-energized
Outside air damper is forced closed
Electric heat stages are de-energized
Fault is indicated
DX PRESSURE FAULT ( )
The DX Pressure Fault will occur when the UVC detects a switch open
condition from the refrigerant pressure switch.
Effect:
Compressor is immediately de-energized
Outdoor fan (if present) is de-energized
Fault is indicated
COMPRESSOR ENVELOPE FAULT ( )
The UVC monitors refrigerant temperatures. The Compressor Envelope
Fault will occur when the UVC detects compressor operation that has
exceeded the allowed operating parameters.
Effect:
Compressor is immediately de-energized
Outdoor fan (if present) is de-energized
Fault is indicated
Cause:
Poor air flow through the refrigerant coils, check fans for proper
RPM, check air filters
If the unit has a 3-phase scroll compressor, check for proper
electrical phasing
Refrigerant circuit component failure or improper adjustment, check
refrigerant pressures and TXV adjustment
Coil sensors may have lost proper contact with the refrigerant coil,
check coil sensors
DISCHARGE AIR DX COOLING LOW
LIMIT INDICATION ( )
The Discharge Air DX Cooling Low Limit Indication will occur when
the UVC detects a low discharge air temperature (DAT < MCLL)
during compressor cooling.
Effect:
Compressor is immediately de-energized
Outdoor fan (if present) is de-energized
Fault is indicated
CONDENSATE OVERFLOW INDICATION (OPTIONAL) ( )
The Condensate Overflow Indication (optional) will occur when the
UVC detects high condensate levels within the units indoor coil drain pan.
Effect:
Compressor is immediately de-energized if in cooling
Outdoor fan (if present) is de-energized
Fault is indicated
SPACE COIL DX TEMP SENSOR FAILURE ( )
The Space Coil DX Temp Sensor Failure fault will occur when the UVC
detects an open or a short condition from the DX temperature sensor.
Effect:
Compressor is immediately de-energized
Outdoor fan (if present) is de-energized
Fault is indicated
OUTDOOR TEMP SENSOR FAILURE ( )
The Outdoor Temp Sensor Failure fault will occur when the UVC
detects an open or a short condition from the OA temperature sensor.
Effect:
Compressor is immediately de-energized
Outside air damper is forced closed
Fault is indicated
DISCHARGE AIR TEMP SENSOR FAILURE ( )
The Discharge Air Temp Sensor Failure fault will occur when the UVC
detects an open or a short condition from the DA temperature sensor.
Emergency heat mode is available during this fault condition.
Effect:
Space fan is immediately de-energized (unless in emergency heat
mode)
Compressor is immediately de-energized
Outdoor fan (if present) is immediately de-energized
Outside air damper is forced closed
Electric heat stages are de-energized
Fault is indicated
OUTDOOR COIL DX TEMP SENSOR FAILURE ( )
The Outdoor Coil DX Temp Sensor (air source self-contained type units
– AZ and AE only) Failure fault will occur when the UVC detects an open
or a short condition from the OA DX temperature sensor.
Effect:
Compressor is immediately de-energized
Outdoor fan (if present) is de-energized
Fault is indicated
SPACE HUMIDITY SENSOR FAILURE (OPTIONAL) ( )
The Space Humidity Sensor Failure fault will occur when the UVC
detects an open or a short condition from the IA space humidity sensor.
Effect:
IA/OA Enthalpy comparison economizer (if used) is disabled
Dehumidification function (optional) is disabled
Fault is indicated
OUTDOOR HUMIDITY SENSOR FAILURE (OPTIONAL) ( )
The Outdoor Humidity Sensor Failure fault will occur when the UVC
detects an open or a short condition from the OA humidity sensor.
Effect:
IA/OA Enthalpy comparison or OA Enthalpy economizer (if used)
is disabled
Fault is indicated