Instruction manual

www. americanwaterheater .com 21
CERTIFIED GAS
SUPPLY FLEX PIPE
(PROPERLY SIZED
FOR THE HEATER
INPUT RATE)
SEDIMENT
TRAP
GAS
CONTROL
VALVE
GROUND
JOINT
UNION
(OPTIONAL)
CAP
3”
MIN.
Figure 13
BLACK PIPE
SEDIMENT
TRAP
GAS
CONTROL
VALVE
GROUND
JOINT
UNION
(OPTIONAL)
CAP
3” MIN.
Figure 14
SEDIMENT TRAP
Contaminants in gas lines can
cause fire or explosion.
Clean all gas piping before
installation.
Install sediment trap in accor-
dance with NFPA54.
Fire and Explosion Hazard
WARNING
A sediment trap should be installed as close to the inlet of
the water heater as practical at the time of water heater
installation. The sediment trap should be either a tee tting
with a capped nipple in the bottom outlet or other device
recognized as an effective sediment trap. If a tee tting is
used, it should be installed in conformance with one of the
methods of installation shown in Figure 13 & Figure 14.
Contaminants in the gas lines may cause improper
operation of the gas control valve/thermostat that may
result in re or explosion. Before attaching the gas line be
sure that all gas pipe is clean on the inside. To trap any
dirt or foreign material in the gas supply line, a sediment
trap (sometimes called a dirt leg) must be incorporated in
the piping. The sediment trap must be readily accessible.
Install in accordance with the “Gas Piping” section. Refer
to the current edition of the National Fuel Gas Code”
(ANSI Z223.1/NFPA 54) .
HIGH ALTITUDE INSTALLATIONS
Installations above 7,700’ . require replacement of the
burner ori ce in accordance with the current edition of
the National Fuel Gas Code” (ANSI Z223.1/NFPA 54).
Failure to replace the ori ce could result in improper and
inef cient operation of the appliance, producing carbon
monoxide gas in excess of safe limits, which could result
in serious personal injury or death. Contact your gas
supplier for any speci c changes which may be required
in your area.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
High altitude orifice must be
installed for operation above
7,700 ft.
Contact a qualified installer or
service agency.
Breathing Hazard - Carbon Monoxide Gas
WARNING