Owner manual

RP/IS-A-4000CIV
Installation, Maintenance, & Repair
Series 4000CIV
Reduced Pressure Zone Assemblies
Sizes: 2
1
2" – 10" (65-250mm)**
4000CIV
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can
result in death, serious personal injury, property damage, or
damage to the equipment.
Keep this Manual for future reference.
Basic Installation Guidelines
NOTICE
The flange gasket bolts for the gate valves should be re tight ened
during in stal la tion as the bolts may have loos ened due to stor age
and ship ping.
High Capacity Relief Series:
Location and Installation Considerations
1. Backflow preventers must be installed in high-visibility locations in
order to allow for immediate notice of telltale discharge or other
malfunction. This location should also facilitate testing and ser-
vic ing, and protect against freezing and vandalism.
2. Installing a backflow preventer in a pit or vault is not rec om-
mend ed. However, if this becomes necessary, Watts highly
rec om mends that a licensed journeyman tradesperson, who is
recognized by the authority having jurisdiction, be consulted to
ensure that all local codes and required safety provisions are
met. An air gap below the relief port must be maintained so as to
avoid flooding and submersion of the assembly, which may lead
to a cross connection. *Please refer to Figure No. 1 for further
information.
3. Pipe lines should be thoroughly flushed to remove foreign mate-
rial before installing the unit. A strainer should be installed ahead
of backflow preventer to prevent disc from unnecessary fouling.
Install valve in the line with arrow on valve body pointing in the
direction of flow.
CAUTION
!
Do not install a strainer ahead of the backflow preventer on seldom-
used, emergency water lines (i.e. fire sprinkler lines). The strainer
mesh could potentially become clogged with debris present in the
water and cause water blockage during an emer gen cy.
4. Normal discharge and nuisance spitting are accommodated by
the use of a Watts air gap fitting and a fabricated indirect waste
line. Floor drains of the same size MUST be provided in case of
excessive discharge. *Please refer to Figure No. 1 and Figure
No. 2 for further in for ma tion.
5. When a 4000CIV Series backflow preventer is installed for dead-
end service applications (i.e. boiler feed lines, cooling tower
makeup or other equip ment with periodic flow requirements),
discharge from the relief vent may occur due to water supply
pressure fluctuation during static no-flow con di tions. A check
valve may be required ahead of the backflow preventer. *Please
see “Troubleshooting”, Page 7, prior to installation.
You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual
is not consistent with local building or plumbing codes,
the local codes should be followed. Inquire with governing
authorities for additional local requirements.
WARNING
!
Need for Periodic Inspection/Maintenance: This product
must be tested periodically in compliance with local codes, but
at least once per year or more as service conditions warrant. If
installed on a fire suppression system, all mechanical checks,
such as alarms and backflow preventers, should be flow tested
and inspected in accordance with NFPA 13 and/or NFPA 25.
All products must be retested once maintenance has been
performed. Corrosive water conditions, and/or unauthorized
adjustments or repair could render the product ineffective for the
service intended. Regular checking and cleaning of the product’s
internal components helps assure maximum life and proper
product function.
WARNING
!
NOTICE
For Australia and New Zealand, line strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
Testing
For field testing procedure, refer to Ames installation sheets
IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on www.
amesfirewater.com.
For other repair kits and service parts, refer to our Backflow
Prevention Products Repair Kits & Service Parts price list
PL-A-RP-BPD found on www.amesfirewater.com.
For technical assistance, contact your local Ames representative.
www.amesfirewater.com
A Watts Water Technologies Company
WARNING
!
The installation and maintenance of backflow assemblies
should be performed by a qualified, licensed technician.
Failure to do so may result in a malfunctioning assembly.
** Metric Dimensions are nominal pipe diameter. This product is produced with
ASME/ANSI flanged end connections or DN flanged end connections.

Summary of content (8 pages)