Manual

7
Installation and Maintenance Manual
Chapter 3: Programming
Where: A = 5 for 5 outputs
= 6 for 11 outputs
= 7 for 17 outputs
= 8 for 23 outputs
= 9 for 29 outputs
Setpoints are in whole numbers (drop decimal).
Example: 12 outputs relays with 10 programs:
S.P. = 1467 -2 = 24.45 - 2 = 22 Setpoints/Program
10 x 6
The following table shows the relationship between the number of outputs, the number of programs, and
the number of setpoints per program. The table only shows a few of the many combinations that are
possible. Before programming outputs, it is advisable to verify that enough setpoints are available, otherwise
the number of programs may need to be reduced. A setpoint is one CIR ON or CIR OFF entry.
STUPTUO5STUPTUO11STUPTUO71STUPTUO32STUPTUO92
352/1242/1702/1181/1161/1
21/0252/993/534/497/2
9/6281/2142/843/525/3
6/6321/7181/0142/703/5
1/797/7241/3102/852/6
äã
Number of program Resulting in number of setpoints per program.
Programming 1995 PLS for Multiprogram
A) Specify the number of programs desired, unit must be in the Program mode. Depress
See above table
for the capabilities of your unit.
B) Upon entering the above sequence, depressing the key will display the
maximum amount of setpoints per program.
NOTE: A time-based output uses up three setpoints.
ENT
CIR#
-
7
-
7 0
-- CIR ON
# of Programs
- ENT-
.
-
CIR OFF