Chapter 3: Programming
17 Outputs = 207 Setpoints Available
23 Outputs = 181 Setpoints Available
29 Outputs = 161 Setpoints Available
Refer to the Section 3.5: Selecting Number of Outputs.
3.12: Electronic Offset
The offset key is used to synchronize the digital display with the actual machine position. The Series
1995B PLS has full scale factor offset capabilities, and the offset is held in nonvolatile memory. How-
ever, to eliminate possible problems in the event that a replacement PLS is required, it is good practice
to mechanically synchronize the resolver with the machine and then use the offset key to make final, fine-
tune adjustments.
Programming the Electronic Offset
A) Unit must be in the Program mode.
B) Stop machine at a known location.
C) Depress . After this sequence is
completed, the display will change to the position entered. The display and outputs are now
synchronized with the actual machine position.
OFFSET (Actual Machine Position) ENT
-
-
3.13: Motion Detector
A programmable Motion Detect output will energize a relay when the transducer speed exceeds the
customers preprogrammed RPM value.
The motion detector is set by entering the following:
A) Unit must be in the Program mode.
B) The motion detect must first be enabled before you can store any values. To accomplish this,
depress . A one (1) will enable the motion
ENT
CIR#
-
5
-
5
-
(0 or 1)
-
ENT
-
detect circuit, and LS5 will now be your motion detect output relay. If a zero (0) is
entered, the motion detect feature is disabled and LS5 will function as a normal limit switch.
C) To set the value at which the motion detect relay energizes, depress
ENT
CIR#
-
1
-
7 6
--
(RPM Value)
-
ENT
-
NOTE: A CIR #176 can only be entered if the motion detect option is enabled.
.