Manual

Chapter 5: Fault Check
Installation and Maintenance Manual
22
5.1: PLS Output Status on Fault Conditions
1) If a fault condition is detected, ALL limit switch outputs will turn off and the display will
show the following:
EE0 = Resolver Not Plugged in or Resolver Primary Open
EE1 = Resolver Secondary S1-S3 Open or Shorted
EE2 = Resolver Secondary S2-S4 Open or Shorted
EE3 = Resolver Shorted - Primary Winding or Resolver Excitation Fault
EE4 = Electronic Transducer Tracking Fault
No Message Microprocessor or 5 Volt Power Supply Failure
The message will remain on the display and the outputs will be off until the problem is
corrected and the fault reset button is pressed and released to reactivate the fault output
and return the display and outputs to their normal operation.
2) If the fault condition is the result of a microprocessor failure or lockup, the state of the
limit switch output circuits cannot be predicted. However, the fault check output will
turn off until the fault is cleared and the fault reset button is pressed and released.
Removal and reapplication of power to the PLS system may clear a locked-up
condition.