Chapter 4: Programming
31
Installation and Programming Manual
Chapter 4: Programming
Count Direction (301)
The Count Direction function is used to change the direction the shut height position will move 
as the LDT’s magnet travels along the guide rail. A 0 value will cause the position to increment 
as the magnet moves away from the LDT head. A value of 1 will cause the position to increment 
as the magnet moves toward the LDT head. The default for this function is 1. For further 
explanations, see Figure 4-2. To change the value of the Count Direction function, perform the 
following steps:
1. Select the function key.
 The monitor displays “F-----”.
2. Select function number 301 . Select the enter key.
 The monitor displays the function’s current value.
3. Enter either a 0 or 1. Select the enter key. 
301
Enter either
0 or 1
Figure 4-2  Count Direction Function
Count Direction Function = 0 Count Direction Function = 1
100
100
When the Count Direction Function is 
programmed with a value of 0, the 
monitor will increment when the LDT’s 
magnet assembly is moving away from 
the head of the LDT.
When the Count Direction Function is 
programmed with a value of 1, the 
monitor will increment when the LDT’s 
magnet assembly is moving toward the 
head of the LDT.
0
0
(F)
8
8