Chapter 4: Programming
35
Installation and Programming Manual
Chapter 4: Programming
Decimal Location (13)
The Decimal Location function is used to program the resolution of the shut height and all 
position data shown on the monitor’s LED display. Resolution can be either displayed in whole 
units, tenths, hundredths, or thousandths. Resolution choices correspond to the following values:  
0 = whole unit; 1 = tenths; 2 = hundredths; and 3 = thousandths. To change the resolution 
shown on the monitor’s LED display, perform the following steps:
1. Select the function key.
 The monitor displays “F-----”
2. Select function number 13. Select the enter key.
 The monitor displays the function’s current value.
3. Enter either a 0, 1, 2, or 3. Select the enter key.
Position Hold (15)
The Position Hold function stops the monitor from displaying irrelevant uctuations during a 
press’s stamping cycle. When the monitor’s auxiliary input is activated, this function will hold 
the last position read. Either a 0, 1, or 2 can be programmed in this function. Entering a 1 will 
cause the monitor to hold the last position read when power is applied to the auxiliary input. 
Entering a 2 will cause the monitor to hold the last position read when power is taken away 
from the auxiliary input. Entering a 0 disables this function. The default for this function is 0. 
Enabling this function disables the Move Detection Time-Out function. When the Position Hold 
function is enabled, the value for the Move Detection Time-Out is then used for the Position 
Hold dwell time. The position hold dwell time is the amount of time the monitor continues to 
hold the shut height position after the auxiliary input is released (or activated, depending on 
the input’s programmed state). To enable or disable the Position Hold function, perform the 
following steps:
1. Select the function key.
 The monitor displays “F-----”
2. Enter function number 15. Select the enter key.
 The monitor displays the function’s current value.
3. Enter either 0, 1, or 2. Select the enter key.
NOTE:  The default time for the position hold dwell may be too long for your application. To 
change this value for your application, perform the following steps. 
15
Enter either 
0, 1, 2, or 3
13
Enter either 
0, 1, or 2
(F)
8
8
(F)
8
8
T13692 Chapter 4.indd 3/17/04, 6:50 AM35