Instruction Manual
3
6
6
3%2)%3
2%,!9
05-034/03
4!.+
%,%#42/$%
(/,$%2
05-034!243
!#,INE
6OR6
OR(Z
4/05-0
34!24%2
#HASSIS'ROUND
4HROUGH-OUNTING3CREW
'ROUNDRETURNTOTANK
ORELECTRODEIFREQUIRED
3ENSITIVITY
2ESISTOR
,OAD
#ONTACTS
6!2)!",%
2%3)34!.#%
0/4%.4)/-%4%2
/04)/.!,!4
%842!#/34
2
PUMP UP
5. Sensitivity Resistor Too Low
If the sensitivity resistor value is too low for the resistance or conductivity of the liquid 
to be controlled, the load relay will not pull in, or it will buzz and chatter before pulling 
in. In either case, the sensitivity resistor should be replaced with a higher value 
resistor (see table, page 2). If in doubt about R1 resistor selection, furnish factory 
with details on liquid, or send sample of liquid for testing.
6. Fouled Electrodes
Accumulation of dirt, oil, grease, or other deposits on the electrodes may insulate 
them and prevent load relay from pulling in. If this occurs, the electrodes should be 
inspected and cleaned at regular intervals, as required, to eliminate the diffi culty. 
If unusual quantities of oil, grease or sludge are encountered, the electrodes can 
be mounted inside a pipe that is fl ushed with clean water. A 4” pipe should be used 
-- with the bottom located below the lowest expected water level, and vent holes 
provided at the top so that the level inside and outside the pipe will be the same. A 
small fl ow of water entering the top of the pipe will cause an outward fl ow of water 
from the bottom of the pipe and prevent undesirable material from entering. Thus, 
the electrodes have a clear surface on which to operate, and will stay clean.
7. Electrodes Too Short
It is possible for an installation to be completed in which the upper electrode is 
suspended at a point where the liquid cannot make contact. All installations should, 
of course, be checked to make sure that the proper electrode lengths are provided. If 
stand pipes are used, make sure pipe is vented above upper electrode setting.
B - One Level Operation
If control operates at one level only (starts and stops at one electrode level) check 
following:
1. Electrode Wires
If wires between control and electrodes are interchanged, load relay will not operate 
over a range in level, but from the lower electrode only. To correct, simply reverse 
electrode connections either at terminal strip or electrode holder.
2. Holding Circuit
If the holding circuit (terminals 4--7) is not closing, the load relay will operate from the 
upper electrode only. If the holding circuit is not opening, the relay will operate from 
the lower electrode only. This holding circuit contact can be checked for continuity 
with an ohmmeter. If defective, and if contacts 2-5-8 are not being used for load 
connections, contacts 5-8 can be used as a holding circuit contact. Move the internal 
jumper from terminal 7 to terminal 8, and move the lower electrode connection from 
terminal 4 to terminal 5.
C - Intermittent Operation
If the control occasionally short cycles or operates intermittently, check the following:
1. Continuously monitor input voltage for fl uctuations or voltage spikes.
2. Check for physical vibration caused by contactors or magnetic starters 
mounted nearby.
3. Check A-4 & A-6.
D - Constant Chatter
If load relay contacts chatter continuously, check defective control as in A-2.
1. If relay now operates correctly, check A-4 & A-6, B; C-1 and C-2.
2. If relay still chatters with terminals 13 & 14 jumpered together, the load relay 
is defective, or the capacitor across the load relay coil may be defective.
E - Load Relay Will Not Drop Out
If relay will not drop out when liquid falls below lower electrode, check the following 
points:
1. Defective Control - See A-2.
2. Grounded Electrode Leads
A ground in the lead wire to the upper or lower electrode will prevent the relay from 
dropping out on low liquid level. 
If the distance from the holder to the control is relatively short, the best way to check 
for ground is to connect replacement wires from the terminal strip to electrode holder, 
outside of conduit, and test for proper operation. If load relay drops out properly, it is 
safe to assume that a ground exists in the original wires to the electrode holder.
If control is located a considerable distance from the electrode holder, check for 
ground as follows: Disconnect power, remove wires from terminals in electrode 
holder, and allow them to stick up in the air to eliminate the possibility of contacting 
a grounded part. Then turn on power. If load relay pulls in, a short is indicated in the 
upper lead wire to ground between the control and the electrode holder.
If the load relay does not pull in , short the relay with a piece of insulated wire by 
bridging between relay terminals 13 & 14. The load relay should pull in when this 
connection is broken. If the relay does not drop out, a short to ground is indicated 
in the lower electrode lead between the control and electrode holder. If any of these 
conditions exist, disconnect the power and replace the grounded wires.
3. Electrode Holder
Excessive dirt or moisture over the insulation at the electrode holder or the 
electrodes can cause faulty operation. The interior of the electrode holder and its 
underside should be kept clean and dry. Conduit connection should be made so that 
no condensation can enter the holder. The underside of vertically mounted holders 
should never come in contact with the liquid. Insulated rod electrodes should be 
used with horizontally mounted holders. Electrodes should be kept clean and free 
of dirt or grease. A periodic check should be made to make sure that they do not 
become fouled with fl oating debris or insulating deposits.
4. Length of Electrode Lead Wire
On installations with excessive distance (over 1,000 feet) between a 5200-LF1 low 
sensitivity control and the tank, capacitance in the lead wires from the control to the 
electrodes may affect normal operation. If wired for direct operation, capacitance 
would cause the load relay to hold in when the liquid leaves the lower electrode. If 
wired for inverse operation, the load relay would fail to pull in. In this event, a 5200-
HF2 high sensitivity control should be used.
Inverse Operation
In inverse operation, the relay is energized when liquid falls below the lower 
electrode, and current ceases to fl ow. Be sure sensitivity resistor has been installed 
between terminals 13 & 14, and a ground connected to terminal 15.
F - Load Relay Will Not Pull In
If relay will not pull in when liquid drops below lower electrode, failure to operate is 
probably caused by one of the following conditions:
1. Power Failure or No Voltage
See Section A-1 under Direct Operation.
2. Defective Controls
To check the relay, disconnect electrode and load connections from relay terminals. 
Apply line voltage to the appropriate terminals, (10 & 11 or 10 & 12), and short 
between terminals 14 & 15 with an insulated jumper wire. The load relay should drop 
out when the jumper is connected and pull in when the jumper is removed. Failure to 
do so indicates a defective control.
3. Grounded Electrode Leads
A ground in the lead wire to the upper or lower electrode will prevent the load relay 
from pulling in . Section E-2 describes how to isolate the grounded wire when the 
relay is being used for direct operation. This same method can be used when the 
control is being used for inverse operation, but the functions must be reversed. (i.e. 
“drop out” interchanged with “pull in”). In section E-2, bridge between terminals 14 & 
15 instead of 13 & 14.
4. Electrode Holder - See Section E-3
5. Length of Lead Wires
Excessive distance will not allow the 5200-LF1 low sensitivity control to operate 
when the liquid drops below the lower electrode. See Section E-4.




