Specifications
Page 40
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
5.14.6 SmartTerminal Controls and Indicators
All controls, except for the Enable / Disable keyswitch, are of a momentary push button style.
Figure 45: SmartTerminal Front Panel Layout
5.14.7 SMARTTERMINAL Screen Format
There are 3 events that can be reported and displayed by SmartTerminal. The types of event are;
1. Fire
2. Faults
3. Disables.
The types of events are only associated with loop devices and detectors hence faults associated
with modules, loops O/C – S/C, power supplies and so forth are not reported on the LCD.
The SmartTerminal has front panel indicators for each type of event. When the SmartTerminal is
configured not to report a type of event and that event type is present (and the corresponding front
panel indicator is illuminated on the SmartTerminal), then a standard information screen is
displayed on the LCD stating the system is not normal and the operator should see the FACP.
FIRE: If configured the screen format for reporting fire condition is:
<point location> FIRE
<point descriptor> <type>
<date> <time> CONTROL*
FIRE XXX OF XXX ZONE
Fault: If configured the screen format for reporting fault condition is:
<point location> FAULT
<point descriptor> <type>
<date> <time> CONTROL*
FIRE XXX OF XXX ZONE
Note: The fault types only relate to devices.