Specifications

Page 41
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
In the event of a loss of communications, for a period of greater than 15 seconds
the LCDA will default to the No Communications screen. The format for this screen
is:
No Communication
Device Isolate / Disables: If configured the screen format for reporting loop / sensor / zone disable
condition is:
<point location> DISABLED
<point descriptor> <type>
<date> <time> CONTROL*
FIRE XXX OF XXX ZONE
Normal / Default: The format for reporting that everything is normal is:
<DATE> <TIME>
<SYSTEM STATUS>
The screen is only displayed when there are no alarms, fault or disables on the panel.
The default screen is only displayed when there are no device alarms, device faults or device
disables present on the system. The highest priority current system status will be displayed and can
be one of the following listed in order of highest to lowest priority:
1. SYSTEM EVACUATE”
2. “SYSTEM FIRE
3. “TRIAL EVACUATION
4. “SYSTEM DBA”
5. “SGD INTERLOCK
6. “SOUNDERS INOPERATIVE
7. “SYSTEM GENERAL FAULT”
8. “SYSTEM PRE-ALARM
9. “SYSTEM EMERGENCY
10. “SYSTEM SECURITY
11. “SYSTEM USER”
12. “SYSTEM DISABLE”
13. “PARTIAL DISABLE
14. “SYSTEM NORMAL”
Config: The Config screen displays the following
VX.X (software version number
Address
A- A+ C- C+
A - , A+ : adjusts the address 1 to 30, 30 being the maximum number of SmartTerminal’s that can
be connected to the FACP, (default is 255 which is not a valid address).
The function keys perform the following;
A press “Previous A+ press “Next”
C - C+: decreases [-] and increases [+] the LCD contrast level.
The function keys perform the following;
C press “Silence Buzzer C+ press “Reset”