Specifications

Page 42
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
5.14.8 Setting the SmartTerminal Controller Configuration in ConfigManager
Right click on the Controller icon and select “Edit Module Typesto bring up the following screen/s.
Figure 46: The Controller Edit / Add Module Types Screens
Click within the check box to “tick” the check box and click OK. Double click on the
Controller to open the Panel screen and the SmartTerminal tab should now be visible along with the
other installed functions.
5.14.9 Setting the SmartTerminal Reporting Parameters in ConfigManager
To set the SmartTerminal parameters click on the SmartTerminal tab and the following screen will
be displayed. Under the assigned SmartTerminal Card designator, 1 to 30, click in the Active box to
change the “N” (NO not fitted) to “Y” (YES fitted) and then enter or type in a “Description”. The
description should be a name given to the SmartTerminal (LCDA) or its physical location. Double
click in each of the “Report” boxes to display and set the, “Y” (Yes reports the parameter) and “N”
(No does not report the parameter) “Alarms, Faults, Disablesparameters that SmartTerminal will
display on each SmartTerminal at each location.
Note: A maximum of 30 SmartTerminal’s can be used in the configuration of the FACP.
Figure 47: Example of SmartTerminal Configuration Settings Screen
Note: In this case SmartTerminal
numbers 6 to 30 are not used.