Specifications
Page 59
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
Is pressed to access SYSTEM STATUS - .For a network panel
Figure 65: Display System Status
AValues:
, for a network panel is pressed to access AVALUES. Enter the Loop number then ENTER
then Sensor number then ENTER.
Figure 66: Analogue Values
9.2 Testing Menu
Is pressed to access the ALARM, FAULT AND LAMP TESTING MENU.
Figure 67: The Testing Menu
9.2.1 Alarm Test
Is pressed to initiate an Alarm Test: Alarm tests either a zone or a sensor on a loop or a range of
zones or sensors on a loop .
This test will force a zone/s or sensor/s to go into the Alarm state or a conventional zone to a
simulated Alarm condition. Pressing ENTER initiates the test. Pressing RESET clears the test.
9.2.2 Fault Test
Is pressed to initiate a Fault Test: Fault tests either a zone or a sensor on a loop or a range of
zones or sensors on a loop in the same way as for the Alarm test above.
This test will force a sensor to go into the Fault state or a conventional zone to a simulated Fault
condition. Pressing ENTER initiates the test.
Once the above tests have been completed the TEST FAILURE screen will appear. Each ALARM
and FAULT that was detected can be viewed by scrolling through them using the
NEXT
and
PREVIOUS
keys. If an Alarm or Fault was not detected a short message displays this result and the
screen returns to the Fault Test default screen.
TESTING MENU
0: ALARM 1: FAULT 2: LAMP
SELECT NO.
AC:3S ALM: 000 PALM: 000 FLT: 000 DIS: 000
Loop 1 sensor 1
L1 S1 Z2 STAT: NORMAL
AVALUE: 25 MODE: 0 I: 000 O:: 000
AC: 2S ALM: 000 PALM: 000 FLT: 000 DIS: 000
SYSTEM STATUS
ALARMS: 0000 PRE-ALARMS: 0000 DISABLES: 0000
DEVICE FAULTS: 0000 MOD FAULTS: 00 WDG: 00
LOOP FAULTS: 00 VERSION: 6.1 EN54
AC: 2S ALM: 000 PALM: 000 FLT: 000 DIS: 000