Specifications

Page 62
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
The type of log, number and totals logged, date and time of the ALARM, FAULT,
DISABLE, SYSTEM or I/O as well as device information will be displayed. The
SYSTEM screen displays events and watchdog activity. From these screens the operator can select
two other facilities, they are;
Press
PRINT ENTRY will print out the displayed information if a printer is installed, or
SHOW OPTIONS allows the operator to select how the Logs are viewed.
Press
To VIEW BY ENTRY NUMBER or to VIEW BY DATE. In each case the screen will ask for
the appropriate information (ENTRY NUMBER or DATE) to be entered before the selected option
will be displayed.
Note: it is possible to scroll through the alarms by using the PREVIOUS and NEXT keys.
10.5 The Function Test Facility
Press TESTS: prompts the operator to select either the WALK or LOOP test.
Press WALK TEST; the operator will be prompted to select either ZONE or SENSOR test.
Press ZONE WALK TEST MENU;
This screen requires the operator to select a Zone or number of Zones to be tested, that is enter the
Zone number pres ENTER or enter the Zone number press TO then the next highest Zone
number o be tested EG. 2 TO 7 then ENTER.
The TEST MODE LED will be illuminated for the duration of the test and the test will run until the
operator RESETS the system or the test times out [Time Out = 15 minutes + 3 to 5 seconds].
Press SENSOR WALK TEST MENU
This screen requires the operator to select a Zone and then a Sensor or (number of Sensors using
the TO key) to be tested then pressing ENTER to start the test.
The TEST MODE LED will be illuminated for the duration of the test and the test will run until the
operator RESETS the system or the test times out [Time Out = 15 minutes + 3 to 5 seconds].
Press LOOP TEST requires the operator to select a LOOP for DIAGNOSTIC TESTING
Entering the LOOP number and pressing ENTER will initiate the DIAGNOSTIC TEST.
Note: The LED’s on the Brigade Board will indicate which leg is being tested.
The tests displayed are;
TESTING SIDE A IDENTIFING DEVICES on SIDE A, and
TESTING SIDE B IDENTIFING DEVICES on SIDE B.
Once the testing is completed the final screen will display the number of devices found and tested on
the LOOP and a Reset is requested to return the system to normal.
Note: If the data is not entered within 2 minutes the screen will time out and return to the
DEFAULT SCREEN.