Specifications
Page 65
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
10.8.1 Conventional Zone Programming
Press Zone:
Key in the zone number and enter or change the description ( DESC ) by
pressing buttons to move the flashing underline or curser. The numeric buttons multiple times to
access characters while at the same time using
Figure 72: Zone Description & Type Programming
Press to move to the TYPE field or edit the information.
Press to move between fields use the reciprocal button
By going through all the fields a second screen can also be accessed to show the Output options.
Press to step through these fields.
Figure 73: Brigade Options
The keys are used to set the Y/N field, which is the selected Zone that will
activate the Brigade Options ALRM, BELL etc and Config.
Figure 74: Zone Configuration Latching / Non-latching
Use or to change the setting
Configuration settings are Latching, Non-Latching, AVF, Self Reset ( 0 to 99 seconds ). After setting
the Configuration the ZONE I/O GROUPS are programmed.
Figure 75: Zone I/O Groups
EDIT Z I/O GROUPS
GROUP1: GROUP2: GROUP3:
GROUP4: GROUP5: GROUP6:
Enter GROUP NO.
AC: 3S ALM: 000 PALM: 000 FLT: 000 DIS: 000
EDIT Z CONFIGURATION
CONFIG: LATCHING
Use < or > to change alarm setting
AC: 3S ALM: 000 PALM: 000 FLT: 000 DIS: 000
EDIT ZX BRIGADE OPTIONS AND CONFIG
ALRM: Y/N BELL: Y/N AUX: Y/N SPRK: Y/N AIF: Y/N
ALARM LED: Y/N CONFIG: LATCHING
Use < or > to change setting
AC: 3S ALM: 000 PALM: 000 FLT: 000 DIS: 000
EDIT Zx DESC AND TYPE STRINGS
DESC < ZONE >
TYPE<
ALPHA KEYS ARE ACTIVE
AC: 3S ALM: 000 PALM: 000 FLT: 000 DIS: 000