Specifications

Page 67
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
10.8.4 Output Programming
Press OUTPUT:
By following the screen prompts as above Add, Edit or Delete an output in a panel or on a loop.
10.8.5 Watchdog
Press This Function provides a counter to record any re-initialisation of the processor. If due to a
software failure the panel is automatically reset then the counter will increment by 1. The maximum
count is 99 after which the counter resets to 00. Pressing will reset the counter. When the panel
is commissioned this counter MUST be reset to 0 as must be the Events Logs.
10.8.6 Self Learn
Self Learn is enabled / disabled in the EEPROM programming. If enabled FireFinder has the
ability to detect extra or missing modules or devices, (that is devices or modules that have been
added or removed) or there has been a change of the type of module or device.
Note: If a change does occur the FACP will take 30seconds to register the event on the LCD
and illuminate the FAULT LED.
10.8.7 Extra Devices Detected
The FireFinder LCD will indicate extra devices have been detected by displaying the screen below
and the FAULT LED will be illuminated.
Figure 76: Resolving Extra Modules and Devices
To resolve select FUNCTION, enter PASSWORD, press and the screen below will appear
Figure 77: Added Module or Device
Select (Selecting presents the PROGRAMMING MENU) then or (as seen below)
then ENTER to ADD the module or device to the configuration, or skip to resolve the changes
manually in the Programming Menu.
Figure 78: Resolving Extra Modules or Devices
0: ADD EXTRA MODULES 1: ADD EXTRA DEVICES
2: DEVICE TYPE MISMATCH 3: MODE MISMATCH
SELECT NO.
AC: 3S ALM: 000 PALM: 000 FLT: 000 DIS: 000
PROGRAMMING MENU
0: RESOLVE EXTRA MODULES AND DEVICES
1: ON SITE PROGRAMMING
SELECT NO.
AC: 3S ALM: 000 PALM: 000 FLT: 000 DIS: 000
FIREFINDER 26/2/2007 08:05:45
EXTRA DEVICES DETECTED
GOTO PROGRAMMING MENU TO RESOLVE
SYSTEM IS NOT NORMAL
AC: 3S ALM: 000 PALM: 000 FLT: 000 DIS: 000