FireFinder Fire Alarm Control Panel Series II (NZS4512) Config Manager Version 6 MAN 2600-2
TABLE OF CONTENTS 1 Page No. About This Manual ............................................................................................................... 1 1.1 Introduction ................................................................................................................ 1 1.2 General Requirements ............................................................................................... 1 1.3 References...........................................................................
5 5.2 5.3 4.6.5 Edit External LED Mimic. .............................................................................. 22 4.6.6 Edit Internal Serial ........................................................................................ 24 4.6.7 Edit Fan Control ........................................................................................... 25 4.6.8 Edit Switch & Indicator.................................................................................. 28 4.6.9 Edit SmartTerminal.
9.2 Application Software: ................................................................................................ 65 9.3 Configuration Software: ............................................................................................ 65 10 Hardware requirements...................................................................................................... 66 11 Configuration Programming ..............................................................................................
FIREFINDER NZ 1 About This Manual 1.1 Introduction CONFIGURATION MANAGER Configuration Manager: Is a software tool designed and written by AMPAC Technologies Pty. Ltd to enable users to create configuration files for transfer to and from the FireFinder Series II Fire Alarm Control Panel. Is a universal program that meets the required standards of several different countries. Has been tested on Windows XP Vista and Win7 operating systems.
FIREFINDER NZ 2 CONFIGURATION MANAGER Installation To install the software insert the first CD into the disk drive and click on the Setup.exe file. ConfigManager will then automatically guide the operator through the installation. To run the program, assuming the icon to the default Program Folder was added during the set-up procedure, click on the icon on the screen.
FIREFINDER NZ 3 CONFIGURATION MANAGER The Functions Manu and Tool Bar Running ConfigManager will bring up a window with a Menu and Tool-bar in the top left hand corner of the screen as shown in the diagram below. Figure 1: The Functions Menu and Tool Bar 3.1 The Menu Bar 3.1.1 File This menu gives access to the following functions: New (Project) [CTRL + N]: Select this option to start a new project. The System Settings dialogue box will appear as a result.
FIREFINDER NZ 3.2 Connect 3.2.1 Connect to FireFinder Series II CONFIGURATION MANAGER This will bring up a terminal window showing communications to and from the FireFinder Series II. Refer to the programming section at the end of this manual for more information. 3.3 Tools 3.3.1 Verify Project (F4) The verify function will verify there are no errors or omissions in the project. 3.3.
FIREFINDER NZ CONFIGURATION MANAGER 3.4.1.1 Colours: The colour of the various elements in the program can be set by selecting this tab. For each Form Type indicated on the right hand side simply click on the indicator and the colours selected will be shown on the left hand side. To modify these colours click on the colour and a colour selection chart will appear. Select the preferred colour, and press OK on the form. Figure 3: The Environment Settings Dialogue Box 3.4.1.
FIREFINDER NZ CONFIGURATION MANAGER 3.4.1.3 Compile: Set options to display the compiled file and to choose whether to validate included text as functions. In most instances these will both be set to be on. Figure 5: Compile Dialogue Box Display Compile File: Selecting this tab option will display the compiled FireFinder Series II file. This means that, after compiling the project the *.dat file is displayed in a window on the screen. This is mainly for the advanced user and is usually not selected.
FIREFINDER NZ CONFIGURATION MANAGER 3.4.1.4 Project Creation: Here 2 lines of default customer text (e.g. name) can be entered. This saves having to enter the company's name for every configuration. Figure 6: Project Creation Dialogue Box Increment Function Copies: Click on the tick box to enable Automatic Backup: Select the timing for automatic periodic backup of the project from the drop down box (5, 15, 30, 45, 60 minutes or NEVER).
FIREFINDER NZ CONFIGURATION MANAGER 3.4.1.5 Communications: This tab will display a page to set the port and methodology used to communicate with the FireFinder Series II.
FIREFINDER NZ CONFIGURATION MANAGER 3.4.1.6 File Association: Tick the check box if the project *.ffc files are to be associated the with ConfigManager United Kingdom. The message displayed on the screen confirms the status Figure 8: File Association Selection Box 3.4.1.7 Apollo Input/Output Once the settings 1 through 6 have been set and a new project has been opened (File / New) the Environment Settings screen will now include the Apollo Input/Output.
FIREFINDER NZ 3.4.2 CONFIGURATION MANAGER Window Figure 10: Window Drop Down Box Cascade: Displays windows stacked and cascading from the top left to the bottom right of the screen. Tile Horizontal: Displays Project and Function windows top edge to top edge. Tile Vertical: Displays Project and Function windows right edge to left edge. Arrange Icons: Arranges minimised image windows within the program screen. Minimise All: Minimise all active windows to the bottom left hand corner of the screen.
FIREFINDER NZ 4 CONFIGURATION MANAGER Creating a New Project To create a new project either click on the New Project Icon on the tool-bar, Ctrl + N or; Figure 12: Selecting a New Project Select: File/ New Project. This will bring up the System settings dialogue box as shown below. Note: Remember the Options / Environmental Settings MUST be entered before starting a new project. 4.1 The Systems Settings Dialogue Box 4.1.
FIREFINDER NZ 4.1.2 CONFIGURATION MANAGER Display settings The display settings, sets the LCD message that will be displayed when the FireFinder Series II LCD is in its normal state. The text on each line may be up to 40 characters long. Figure 14: The Display Settings Dialogue Box 4.1.3 Quick Set settings This option will save a considerable amount of work as it will automatically set up the required number of panels, DGP’s and / or mimics.
FIREFINDER NZ 4.1.4 CONFIGURATION MANAGER System (SmartGraphics) Interface The check box is selected if a SmartGraphics Interface is fitted to the system. “Map” allocation can be added later once the interface is selected Figure 16: The Quick Set Dialogue Box 4.2 The New Project Screen When all of the options above have been determined and the OK button has been clicked the following screen will be displayed. This may vary depending on the options selected in the layout options dialogue box.
FIREFINDER NZ 4.3 CONFIGURATION MANAGER The Project View The screen below is a typical view that will be seen by the operator when a single panel is to be programmed. The Panel represents the hardware which is common in all panels. C1 represents the controller that interfaces with up to 8 slave modules. Note: It is recommended that the panel section is programmed first followed by the controller.
FIREFINDER NZ 4.4 CONFIGURATION MANAGER Panel Settings or Editing Double click on the Panel to set or edit the Panel configuration, Main Information, Brigade Signalling Board, Call point / DBA and the Bell Sounder Boards. Note: Click on OK to go to or return to the main project screen at any time. 4.4.1 Main Information Figure 21: Panels Settings - Main Information Description: Default is Panel 1.
FIREFINDER NZ 4.4.2 CONFIGURATION MANAGER Brigade Signaling Board Figure 22: Panels Settings - Brigade Signaling Board Fitted: Click on the box (ticked) if the board is fitted. (Default selected) Alarm relay normally energised: If the relay is to be normally energised click on the check box (ticked). (Default not selected) Fault Relay normally energised: If the relay is to be normally energised click on the check box (ticked). (Default selected) Monitor Warning output: If ticked Monitor this O/P.
FIREFINDER NZ 4.4.3 CONFIGURATION MANAGER Call Point / DBA Shown is the Manual Call Point selected screen. By default the MCP if OFF Note: (For information only NOT USED IN EN54 PANELS) Figure 23: Panels Settings - Call Point / DBA Manual Call Point: Click on the check box (ticked) to enable the MCP. (Default OFF) OFF: Click to disable the selection. (Default) Desc: Type in a name or description / location of the MCP.
FIREFINDER NZ 4.4.4 CONFIGURATION MANAGER Bell Sounder Boards This option allows the user to select a number of Bell/Sounder output boards to be fitted to the panel. These boards allow a larger number than normal, of bells and sounders to be connected to the FireFinder Series II System. In the Bell Sounder Board screen the type of Sounder Board is selected and Sounder Groups are entered into the O/P columns. Bell Sounder Boards are built in two versions: 1.
FIREFINDER NZ 4.5 CONFIGURATION MANAGER Network Parameters: Right click the Panel Icon and select Edit Network Parameters to set Global Access or access for the Panel, Loops and / or Groups. Figure 25: The Panel Access or Network Parameters Screens If Global Access is assigned to a Panel, DGP or mimic they will see or monitor the entire system. If it is not set then the various panels, Loop/s and Group/s will have to be assigned by way of the Set Access screen.
FIREFINDER NZ CONFIGURATION MANAGER 4.6 Controller Configuration 4.6.1 Setting or Editing the Controller Module Types: Right click on the Controller and select “Edit Module Types” from the drop down screen. Using the “Classic” screen click the down arrow within the “Type” column to display the drop down box from which the module type is selected by clicking on it. The Description and Ref [Reference] No [Number] is automatically assigned. Alternatively the “Graphic” screen can be used.
FIREFINDER NZ 4.6.3 CONFIGURATION MANAGER Controller Setting or Editing The following screens have been compressed for the purposes of explanation Edit Modules Apollo and Conventional: To physically edit each parameter left click in the appropriate square and enter or change the existing setting / information. Both drop down screens are shown displayed, this is for explanation purposes only.
FIREFINDER NZ 4.6.4 CONFIGURATION MANAGER Adding More Controllers / Adding More Modules Adding more Controllers, C2, C3, C4, facilitates the addition of more modules which again have to be set in the Classic or Graphic screens. Note: SmartTerminal, is only available to Controller 1 (C1) in both protocols and will be shown to be shaded out, as seen below, to indicate this. Figure 32: Controller Config C1 Edit Module Types (Graphic Screen) 4.6.5 Edit External LED Mimic.
FIREFINDER NZ CONFIGURATION MANAGER Note: The following screens are for demonstration purposes only as only one 1 “Edit Input” selection box will appear at any one time.
FIREFINDER NZ 4.6.6 CONFIGURATION MANAGER Edit Internal Serial Click on the “Tab” Internal Serial and the Edit screen will be displayed. Type: Click within the box to access the drop down screen and select the type of board, in the example shown a Relay Board has been selected. Output: Double click within a box to edit the type of input that will turn the output on. In the example screen a Relay Board has been assigned O/P 1 has been set to be turned on by an Alarm Assigned Point.
FIREFINDER NZ 4.6.7 CONFIGURATION MANAGER Edit Fan Control Click on the “Tab” Fan Control and the Edit screen will be displayed.
FIREFINDER NZ CONFIGURATION MANAGER Figure 40: Fan Alarm and Fan Inhibit editable Inputs Figure 41: Fan Start editable Output Figure 42: Run / Stop / Fault Editable Inputs
FIREFINDER NZ CONFIGURATION MANAGER Figure 43: Latch Reset Screen
FIREFINDER NZ 4.6.8 CONFIGURATION MANAGER Edit Switch & Indicator Click on the “Tab” Switch & Indicator and the Edit screen will be displayed.
FIREFINDER NZ 4.6.9 CONFIGURATION MANAGER Edit SmartTerminal Click on the “Tab” SmartTerminal and the Edit screen will be displayed. To set the SmartTerminal parameters click on the SmartTerminal tab and the following screen will be displayed. Under the assigned SmartTerminal Card designator, 1 to 30, click in the Active box to change the “N” (NO not fitted) to “Y” (YES fitted) and then enter or type in a “Description”.
FIREFINDER NZ CONFIGURATION MANAGER 4.6.10 Single Panels If the system consists of a single panel and a single Controller then commence the configuration by right clicking on the (C1) Controller and selecting Edit Module Types or double left click on the Controller.
FIREFINDER NZ 5 CONFIGURATION MANAGER The Module Data Entry Spreadsheet Once all the Module data for the panel has been entered, the next step is the entry of specific data for each module. This is done via the Module Data Entry Spreadsheet. To access the Spreadsheet double click on the Controller (C1) Note: If the Controller Configuration Information has not been entered the Controller Configuration Dialogue Box will appear rather than the spreadsheet shown below.
FIREFINDER NZ CONFIGURATION MANAGER Figure 49: Zone Configuration (Zone Cnfg) Type If a device is selected, such as I/O Modules, that requires programming or settings the “More” column will indicate this by automatically inserting a in the column. Double clicking on the will open another screen in which control data for that device can be entered.
FIREFINDER NZ 5.1.1 CONFIGURATION MANAGER Specific Device Settings Example of setting devices to a specific Zone Config; XP95 Thermals: Heat A: Specifies XP95 Thermal Type A device is fitted (Rate of rise). Heat B: Specifies XP95 Thermal Type B device is fitted (Fixed). AAM Modules: Investigation Alarm: Allows for an investigation period before the device goes into full alarm. 5.1.
FIREFINDER NZ CONFIGURATION MANAGER Mode 2: General Purpose: If the I/O device is configured as ‘General Purpose’ then each input of that device has its own unique sub address on the physical device. The common outputs on the loop main configuration window become non-functional and all values are taken from the sub address window for the I/O device. This window is opened by clicking on the plus [+] symbol in the more column and allows the configuration of the inputs to be set e.g.
MODULE EDIT NOTEPAD EDITOR COMMS WITH FIREFINDER TRANSFER W INDOW REMOTE CONTROLLER INCLUDED TEXT EDITOR FUNCTIONS VIEW PROJECT VIEW NEW PROJECT OPEN EXISTING PROJECT VERIFY PROJECT CUT C OPY PASTE FILL UNDO EDIT DESCRIPTIONS, GROUPS BRIGADE SECTIONS I/O SETINGS DAY/NIGHT ADD DEVICE 5.
FIREFINDER NZ 5.2.1 CONFIGURATION MANAGER File New (Project) [CTRL+N]: Select this option to start a new project. The “Project Manager” dialogue box will appear as a result. Open [CTRL+O]: Open loads a previously saved project. The “Open Project” dialogue box will appear, locate the file to be opened and click on Open. Configuration Files are saved with the .ffc extension. Reopen: Re-open allows the user to select from a list of previously opened files.
FIREFINDER NZ 5.2.2 CONFIGURATION MANAGER Edit Undo [Ctrl+Z]: This will take the operator back one step in case an error has been made or a change is required while entering data into the Module Data Entry Spreadsheet. Undo can go back up to 20 steps. Holding down Ctrl and pressing Z will also implement this function. Delete [Del]: This will clear a highlighted area on the spreadsheet.
FIREFINDER NZ 5.2.3 CONFIGURATION MANAGER Search Search: This option allows the operator to search for text when editing modules. Search Again F3: This allows the user to search for text again. Replace In Description: This option allows the user to replace letters or words in the description fields. 5.2.4 View Figure 53: The Drop Down Screen & The Highlight Option Menu Add Highlights: When this option is selected the following box appears.
FIREFINDER NZ CONFIGURATION MANAGER The following three options from the View drop down screen if selected takes the operator directly to the appropriate working screen. Another method of selecting these options is to left click on the icons as shown below. (Only applicable if Apollo Module fitted and selected) Edit descriptions, groups, brigade settings. View input / output settings Edit day / night settings. 5.2.
FIREFINDER NZ 5.2.6 CONFIGURATION MANAGER Clicking Icons Project: View displays the current project screen Functions: View displays the Functions screen Connect to FireFinder Series II: This will bring up Transfer Wizard window showing communications to and from the FireFinder Series II. Refer to the programming section of this manual for more information.
FIREFINDER NZ 5.3 CONFIGURATION MANAGER Apollo Modules Selecting an Apollo module tab on the Module Data entry Spreadsheet will display the page for entering the data for that module. The tool bar will also have the following buttons made active. Edit description, groups, brigade settings View input / output settings Edit day / night sensitivity settings Add device to currently selected address Select the tool for the settings you wish to enter. 5.3.
FIREFINDER NZ CONFIGURATION MANAGER Type: The type of device is selectable from a drop down list box. Note: Along with other devices FastSense is selected from this drop down box. Type Descr (Description): The type descriptor is automatically entered by the program. This may be modified if required but it is limited to 6 characters.
FIREFINDER NZ CONFIGURATION MANAGER Groups: The next six columns allow the user to enter up to 6 group numbers against each device. These group numbers are only used for I/O programming. Map: If graphics have been installed this column will be active and display the graphics page the device will be displayed. 5.3.2 Input/Output Settings If there is any device on the loop which has input or output, select the Input/Output icon for I/O Module or the More Settings page.
FIREFINDER NZ CONFIGURATION MANAGER Figure 58: The Module Apollo I/O View and Print Screen Note: To edit this information / screen return to the Edit Sensor Properties, double click on the More + box then edit in the new screen, returning by exiting in the normal way. Fig 1: Module Edit I/O Screen Sens: The Sensor number is set and cannot be modified. Description: The description is limited to 33 characters and may contain numbers or characters.
FIREFINDER NZ 5.3.3 CONFIGURATION MANAGER Day/Night Settings If Day/Night settings are not required then this section may be ignored. If they are required select the icon and the screen below will be displayed. Figure 59: The Day / Night Settings page (Note Sensitivity & Mode Default Settings) To activate the day/night settings on a device, click in the Day/Night column in the spreadsheet, this will toggle between Y and N, set the entry to Y.
FIREFINDER NZ 5.4 CONFIGURATION MANAGER Conventional Modules Selecting a Conventional Module tab on the Module Data entry Spreadsheet will display the page for entering the data for that module. Figure 60: The Conventional Module Settings Page Circuit: The circuit number is set and cannot be modified. Zone: The zone number must be a number between 1 and 999. Description: The description is limited to 33 characters and may contain numbers or characters.
FIREFINDER NZ 5.5 CONFIGURATION MANAGER Input/Output Modules Selecting an Input/Output module tab on the Module Data entry Spreadsheet will display the page for entering the data for that module. The tool-bar will also change to include the Inputs and Outputs buttons.
FIREFINDER NZ 5.6 CONFIGURATION MANAGER SmartTerminal To set the SmartTerminal Annunciator parameters click on the tab and the following screen will be displayed. Under the assigned SmartTerminal Card designator, 1 to 30, click in the Active box to change the “N” to “Y” and then enter a “Description”. Double click in each of the “Report” boxes to display and set the, “Y” yes and “N” no “Alarms, Faults, Disables” parameters that the SmartTerminal will display on each SmartTerminal at each location.
FIREFINDER NZ 6 CONFIGURATION MANAGER Functions This section of the program allows the operator to enter data that will allow the panel to activate outputs in accordance with the pre-determined conditions of specified alarm devices or inputs. Function Icon 6.
FIREFINDER NZ CONFIGURATION MANAGER New Functions: As seen above by selecting this icon a box will appear on the screen with a selection of functions that can be scrolled through or by selecting the arrow head a complete list will be presented. Clone Function n Times: This option allows the operator to create the selected number of copies. Using the Project Creation tab of the Environment Settings you can select weather the cloning of a function automatically increments the entries in each selected box.
FIREFINDER NZ CONFIGURATION MANAGER Note: For a full explanation of each Function refer to the Functions Manual To configure a function, select Functions / New function. This will bring up a Function window as shown below. Each function will have its own Function Window. This graphically displays all the elements of the function. Up to 4 Windows can be opened at once, although you may have as many functions as you require in the system.
FIREFINDER NZ CONFIGURATION MANAGER Once you have brought up a functions window, the functions menu and tool-bar will change to provide you with what you require while working on functions. Each box in the functions window represents a logical part of the function. If it is required make sure the check box in its top left-hand corner is ticked. If you do not require it uncheck the box and that logical component will not take part in the function.
FIREFINDER NZ 7 CONFIGURATION MANAGER Expanding the System The basic FireFinder Series II has the capacity to support up to eight slave CPU’s which in turn may be any one of the three types of hardware mentioned, Apollo XP95 loops, Conventional zones or Input/Output boards. In addition to these other types of configurations are possible. On the tool bar shown below there are a number of items that can be selected and added to the basic configuration.
FIREFINDER NZ 7.2 CONFIGURATION MANAGER Adding a Data Gathering Point To add a Data Gathering Point to the system left click on the DGP icon as shown so that is highlighted. Then left click on the mimic and the DGP will be added. Figure 65: Adding a Data Gathering Point (DGP) Screen Once added, double click on the DGP to open the screen shown below. Here the description and the node numbering (Reference) of the DGP can be edited. In practice it is best to rely on the autonumbering of “Reference”.
FIREFINDER NZ 7.3 CONFIGURATION MANAGER Adding an LCD Mimic To add an LCD Mimic to the system left click on the mimic icon as shown so that is highlighted. Then left click on the project area of the centre screen and the mimic will be added. Figure 67: Adding an LCD Mimic Screen Note: the Node address has been automatically set, e.g. N2 in the above illustration. To display an address that has already been set access the LCDR via the “debug “port, go to “Application Mode” and type in DA.
FIREFINDER NZ CONFIGURATION MANAGER Figure 68: Panel, Loop, Group and Global Access screens 7.3.2 Panel, Loop or Group Access If Global access is not selected then the user has the option to select any combination of Panels, Loops or Groups. This option allows the user then to determine what parts of the system any node may display, test, or affect the I/O (cause and effect). The LCD access may be set to Global, Panel, Loop, or Group access.
FIREFINDER NZ 7.4 CONFIGURATION MANAGER Adding Modules to a Panel To add to a Panel left click on the Add Modules icon as shown so that is highlighted. Then left click on the Panel and the Modules will be added. The types of modules and their operating parameters will then have to be entered. This is achieved by left clicking on the C2 icon on the screen and setting them through the Controller Configuration “Classic” or “Graphic” pop up screens.
FIREFINDER NZ CONFIGURATION MANAGER Figure 72: The Controller Edit Module Types Classic and Graphic Screens The screens shown here are for C1 with Smart Terminal C2 will have the same screens except there will be no SmartTerminal available.
FIREFINDER NZ 7.5 CONFIGURATION MANAGER Adding a High Level Interface (HLI) Another item that may be selected and added to the system is a HLI. To add a HLI to the system left click on the HLI icon as shown so that is highlighted. Figure 73: Adding a HLI Depending upon the configuration of the system a HLI may be fitted by left clicking on any controller be it a LCD mimic or Panel. To delete the interface right click on it and select DELETE.
FIREFINDER NZ CONFIGURATION MANAGER Figure 75: Graphic System Interface Settings Graphics System Interface: Provides for a 2 way interface for the Ampac SmartGraphics system Note: Only One Graphic System Interface per Controller Figure 76: MODBUS Interface Setting MODBUS Interface: Provides for a 2 way intelligent Modbus RTU standard interface for BMS and PLC based systems Note: Only One MODBUS Interface per Controller Figure 77: EV3000 HLI Settings EV3000 HLI: Provides for connection to an AMPAC EV
FIREFINDER NZ CONFIGURATION MANAGER Editable Settings for HLI Board Rate: = Physical Interface: = Handshaking: = Protocol: = 2400 4800 9600 19200 38400 RS232 full Duplex RS485 Half Duplex None Hardware RTS / CTS Software X on / X off. Text Positive Acknowledge EWS – EV3000 The HLI is used to output data to external systems such as Building Management Systems (BMS) in a high level serial format.
FIREFINDER NZ 7.6 CONFIGURATION MANAGER Data Output The data output consists of a string of characters as detailed: Format 1: G (No Descriptor string available) Format 2: Z (Descriptor string available for conventional zones. If a group of sensors share a common zone number but not with a conventional zone then no descriptor is available).
FIREFINDER NZ 7.
FIREFINDER NZ 8 CONFIGURATION MANAGER Network Panels Networked panels are configured in a similar way to an individual panel. In a network each panel is configured with the hardware that is fitted into that particular cabinet (in the same way a stand – alone panel is). The main difference is the access levels that are set for each panel. Figure 78: Networked Panels, DGP’s, Mimics and Controllers Again click on each controller to set its parameters.
FIREFINDER NZ 9 CONFIGURATION MANAGER Introduction to Programming The FireFinder Series II Fire Alarm Control Panel may be programmed from a computer / laptop either directly or via a modem. This manual outlines a number of programming options available to the operator. There are three areas of software that will be discussed as well as single panel programming and network programming. All of the software except for the BOOT software is stored in FLASH memory.
FIREFINDER NZ 10 CONFIGURATION MANAGER Hardware requirements The FireFinder Series II can be configured and updates to the software made via the serial port (RS232) on the Main Board (302-674). If you are using a PC running Windows you can use AMPAC’s ConfigManager program to communicate with the FireFinder Series II.
FIREFINDER NZ 11 CONFIGURATION MANAGER Configuration Programming There are two methods that may be used to load the software into the FACP. Method 1 uses the “Transfer “Wizard” window - Method 2 “uses the Terminal window. The more experienced users tend to use the Terminal window. This requires them to remember commands such as GD etc. For novices using the transfer wizard means that they do not need to remember these commands.
FIREFINDER NZ 11.1 CONFIGURATION MANAGER Transfer – Transfer Wizard Once the Transfer Wizard has established the status of the FACP prompts will guide the operator through the transfer process. If the Transfer Wizard is unable to establish the state of the FACP an error message will be displayed instructing the operator to “Click ‘Back’ to try again”. Figure 82: Transfer Wizard Screen 11.1.
FIREFINDER NZ 11.2 CONFIGURATION MANAGER Uploading In order for the user to upload or download config software it is necessary for the operator to switch to the diagnostics mode. The normal panel operation is halted in this mode and the display will turn off. The command for this is gd. Once this mode has been accessed it is possible to upload a configuration file, select Transfer / Retrieve in ConfigManager and receive the respective file.
FIREFINDER NZ 11.5 CONFIGURATION MANAGER Boot Mode To Change Application Software The Boot mode is used to enable the operator to enter the command area (or Boot mode) of the software where it is possible to replace the application software of the panel. This area should only be accessed when you are replacing the application (or core) software. TYPE BT (BOOT) Panel will enter the BOOT mode. CAUTION: This area allows you to reprogram the application software.
FIREFINDER NZ CONFIGURATION MANAGER Once programmed successfully the following message will be displayed. Ensure that there are no errors when the messages are displayed. If there are errors reported reload the software. Once the software has been successfully programmed into FLASH then the panel is returned to the Diagnostics mode by typing GD (Go Diagnostics).
FIREFINDER NZ CONFIGURATION MANAGER From here if the configuration data has been programmed then type GA (Go Application) and the panel should re-boot. If the system is OK then the message displayed should be similar to below but considerably longer.
FIREFINDER NZ 11.6 CONFIGURATION MANAGER Using a Modem You can communicate with the FireFinder Series II over a modem using HyperTerminal or any number of communication packages. Install the modem on your computer as instructed by the modem manufacturer. In HyperTerminal, under File/Properties, instead of selecting a port (Connect using), select the modem. Ensure that the phone number to ring is the number for the line connected to the FireFinder Series II’s modem.
FIREFINDER NZ 12 CONFIGURATION MANAGER Network Programming Single Point Programming FireFinder Series II is the term AMPAC uses to describe the method by which the network is programmed from one point. It is most important to follow these steps to ensure trouble free network programming. 12.1 Part 1: Upgrading the Configuration Before attempting network programming from a single point you should first check the communications loop and make sure that all panels are operating normally.
FIREFINDER NZ 12.3 CONFIGURATION MANAGER Network Go Diagnostic (NGD) This command causes the entire network to enter the Diagnostic state. QP Note: THIS IS MOST IMPORTANT THAT ALL OF THE PANELS ARE IN THIS MODE. If they are not then it is likely that the panels are not communicating. This must be corrected before proceeding.
FIREFINDER NZ CONFIGURATION MANAGER Once the panels are all in diagnostic mode proceed as below. Send the new config to the panel to which you are connected using your communication package file transfer as you would normally: It is important to take note of the output during programming and make sure that no errors are reported. Once this is done the host panel has been programmed with the latest configuration.
FIREFINDER NZ CONFIGURATION MANAGER NPC A short time after entering the NPC command you should receive a “programmed successfully” message for each controller (except the one that you are programming from).
FIREFINDER NZ CONFIGURATION MANAGER Once the system power up is complete use the QP command to verify that all nodes and controllers are operational: QP
FIREFINDER NZ 12.4 CONFIGURATION MANAGER Part 2: Upgrading the Application Note: If a system is to be upgraded to version 6 from an earlier version then the panels have to be upgraded individually. THIS INCLUDES BOOT ROMs Before attempting network programming from a single point you should first check the communications loop and make sure that all panels are operating normally.
FIREFINDER NZ CONFIGURATION MANAGER NGD This command may take up to 30 seconds to complete on a larger network.
FIREFINDER NZ CONFIGURATION MANAGER BT Send the new application to the panel using your communication package file transfer as you would normally: It is important to take note of the output during programming and make sure that no errors are reported.
FIREFINDER NZ CONFIGURATION MANAGER GD Check the status of the system using the QP command: QP Note: THIS IS MOST IMPORTANT THAT ALL OF THE PANELS ARE IN THIS MODE. If they are not then it is likely that the panels are not communicating. This must be corrected before proceeding. Once the panels are all in diagnostic mode proceed as below.
FIREFINDER NZ CONFIGURATION MANAGER NSA Sending the application software around the network When you enter the NSA command the “Sending Application” dialogue will appear and the offset will increase in value until it reaches the Application Size. At this point the “Down Load Complete” message will appear as well as file received confirmations for each controller and NIC on the network.
FIREFINDER NZ CONFIGURATION MANAGER GA Once the system power up is complete use the QP command to verify that all nodes and controllers are operational: QP
FIREFINDER NZ 13 CONFIGURATION MANAGER Help Commands The following lists of commands are dependent upon the software version of the panel as not all of the commands are supported prior to Version 6. In the normal running mode of the panel there are several help commands that are available if required. By typing “he” and pressing enter, the following list of commands will appear. 13.1 Application Mode Help Commands (he) bf n bi n bo n bm bt gd qv wb 13.
FIREFINDER NZ 13.
FIREFINDER NZ 14 CONFIGURATION MANAGER Troubleshooting Symptom The Laptop Displays Atv0e0s0=2 Possible Cause This is caused by the wrong cable being use between the FireFinder Series II and the laptop. Use a straight dte cable (rd,td,gnd) Remedy Use correct cable An error is reported when using the PC or PA commands The file has an error or there has been an error in transmitting the file Reload the file.
FIREFINDER NZ 15 CONFIGURATION MANAGER Decimal – Hexadecimal – Binary Conversion Table Decimal 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Hex 0 1 2 3 4 5 6 7 8 9 a b c d e f 10 11 12 13 14 15 16 17 18 19 1a 1b 1c 1d 1e 1f 20 21 22 23 24 25 26 27 28 29 2a 2b 2c 2d 2e 2f 30 31 32 Binary 00000000 00000001 00000010 00000011 00000100 00000101 00000110 00000111 00001000 00001001 00001010 00001011 00001100 0000
FIREFINDER NZ Decimal 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 Hex 97 98 99 9a 9b 9c 9d 9e 9f a0 a1 a2 a3 a4 a5 a6 a7 a8 a9 aa ab ac ad ae af b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 ba bb bc bd be bf c0 c1 c2 c3 c4 c5 c6 c7 c8 CONFIGURATION MANAGER Binary 10010111 10011000 10011001 10011010 10011011 10011100 10011101 10011110 10011111 10100000 10100001 101000
FIREFINDER NZ 16 CONFIGURATION MANAGER Certification Information The FireFinder Series II™ is designed and manufactured by: AMPAC TECHNOLOGIES PTY LTD 7 Ledgar Rd Balcatta WA 6021 Western Australia PH: 61-8-9201 6100 FAX: 61-8-9201 6101 Manufactured to: Certificate of Compliance Number: Equipment Serial Number: Date of Manufacture: (HEAD OFFICE)
FIREFINDER NZ 17 CONFIGURATION MANAGER Definitions Addressable system: a fire alarm and detection system that contains addressable alarm zone facilities or addressable control devices. Alarm Verification Facility (AVF): that part of the FACP, which provides an automatic resetting function for spurious alarm signals so that they will not inadvertently initiate Master Alarm Facility (MAF), or ACF functions.
FIREFINDER NZ CONFIGURATION MANAGER UNCONTROLLED DOCUMENT NOTE: Due to AMPAC’s commitment to continuous improvement specifications may change without notice.