Specifications
FIREFINDER NZ
CONFIGURATION MANAGER
4.4.2 Brigade Signaling Board
Figure 22: Panels Settings - Brigade Signaling Board
Fitted: Click on the box (ticked) if the board is fitted. (Default selected)
Alarm relay normally energised: If the relay is to be normally energised click on the check box
(ticked). (Default not selected)
Fault Relay normally energised: If the relay is to be normally energised click on the check box
(ticked). (Default selected)
Monitor Warning output: If ticked Monitor this O/P. (Default not selected)
Monitor Fault O/P: If ticked Monitor this O/P. (Default not selected)
Monitor Bell O/P: If ticked Monitor this O/P. (Default selected)
Monitor Auxiliary O/P: Click on the check box (ticked) if O/P is to be monitored. (Default not
selected)
Door Switch Fitted: Ticked if Door Switch fitted (Default Selected)
SGD Fitted: Ticked if a Signal Generating Device is Fitted (Default Selected)