Specifications

FIREFINDER NZ
CONFIGURATION MANAGER
4.4.3 Call Point / DBA
Shown is the Manual Call Point selected screen. By default the MCP if OFF
Note: (For information only NOT USED IN EN54 PANELS)
Figure 23: Panels Settings - Call Point / DBA
Manual Call Point: Click on the check box (ticked) to enable the MCP. (Default OFF)
OFF: Click to disable the selection. (Default)
Desc: Type in a name or description / location of the MCP. (Default “FRONT PANEL MANUAL
CALL POINT”)
Zone: Allocate the Zone that the MCP will be associated with. (Default = 1)
Page: Displays the “page” in SmartGraphics that the MCP will appear on. (Default not shown
unless SmartGraphics have been added to the system)
Groups: Enter the Group/s to be coupled to the MCP. (Default = 0)
Config: Sets the operation of the MCP to “Latching” or “Non-latching”. (Default = Latching)
Alarm LED: Check (tick) if the MCP is to operate that output / LED. (Default selected)