Specifications

FIREFINDER NZ
CONFIGURATION MANAGER
5.6 SmartTerminal
To set the SmartTerminal Annunciator parameters click on the tab and the following screen will be
displayed. Under the assigned SmartTerminal Card designator, 1 to 30, click in the Active box to
change the “N” to “Y” and then enter a “Description”. Double click in each of the “Report” boxes to
display and set the, “Y” yes and “N” no “Alarms, Faults, Disables” parameters that the SmartTerminal
will display on each SmartTerminal at each location.
Note: A maximum of 30 SmartTerminal’s can be used in the configuration of the FACP.
Fig 2: Example of SmartTerminal Configuration Settings Screen
In the above example Card 1 & 2;
Are active
Are situated in the designated factory floor area 8
Will display all Alarms
Will not display any Faults, and
Will not display any Disables
Card 3
Is active
Is situated in the stores area
Will display all Alarms
Will display any Faults, and
Will not display any Disables
Card 4 & 5
Are active
Are situated in the security areas
Will display all Alarms
Will display any Faults, and
Will display any Disables