Specifications
FIREFINDER NZ
CONFIGURATION MANAGER
12.4 Part 2: Upgrading the Application
Note: If a system is to be upgraded to version 6 from an earlier version then the panels have to
be upgraded individually. THIS INCLUDES BOOT ROMs
Before attempting network programming from a single point you should first check the
communications loop and make sure that all panels are operating normally. It is also essential that
all panels on the loop contain a valid configuration and address for the network that they are
connected to.
It is recommended that all SP programming be carried out from Node 1 (the main panel).
Establish the state of the Network and ensure the loop is good using the QP (Query Points)
command:
QP
Bring the entire system back to diagnostic mode by using the NGD (Network Go Diagnostic)
command: