User manual

Page 18
LOOPSENSE EN54
USER MANUAL
6.1.1 Generic Point Selection Screens
Within the menu system there are several instances in which points are required to be selected in
order to proceed further and display and/or manipulate the selected points. Points include Zones,
Loops, Devices, Device Sub-Addresses, Panel Inputs, Panel Outputs and Add-Ons.
6.1.2 Zone Point Selection
Zones 1 up to 999 can be selected.
SELECT ZONE: XXX
<selected zone descriptor>
►Z1 Z2 Z3 Z4 Z5
Z6 Z7 Z8 Z9 Z10
Zone Address Prefixes:
Z - Zone configured
X - Zone not configured
Zone Address Suffixes:
*- Zone Disabled
S - Zone Sounders Disabled
6.1.3 Loop Point Selection
Loop 1 or 2 can be selected.
SELECT LOOP: X
<selected loop descriptor>
►L1 L2
This screen will be skipped if there is only one loop configured in the system except for in the
programming menu where the prefix “L” next to the loop number will be replaced with an “X if the
loop is not configured and it can be selected to configure the loop. The loop number suffix “*”
indicates that the loop has been disabled.
6.1.4 Loop Device Point Selection
Apollo device addresses 1 to 126 can be selected.
SELECT DEVICE: XXX <device type>
<selected device descriptor>
►D1 D2 D3 D4 D5
D6 D7 D8 D9 D10
Device Address Prefixes:
D - Device configured and fitted
M - Missing device configured and not fitted
T - Type mismatch configured and fitted with incorrect type
E - Extra device not configured but fitted
X - Device not configured and not fitted
Device Address Suffix:
- Device Disabled
6.1.5 Sub-Address Point Selection
Apollo loop device sub-address inputs
1-3 and outputs 1-3 can be selected.
SELECT SUB ADDRESS: X
<selected sub address descriptor>
1I/P1 2:I/P2 3:I/P3 4:O/P1 5:O/P2
6:O/P3
Sub-Address Prefixes:
I/P Sub-Address Input
O/P Sub-Address Output