User manual

Page 40
LOOPSENSE EN54
USER MANUAL
The activation mode choices are:
EVACUATE
ALERT
ALERT TIMEOUT EVACUATE
DELAYED
GLOBAL <action type>
ACTIVATION DELAY: 30 (0-999 Sec)
#CLEAR
◄BACK NEXT►
The activation mode screens are repeated for all action types in which the delays can be edited
The user is then prompted to save any changes that may have been made.
7.6.4.2 Menu->Programming->Sounders->Zone Activation
SELECT ZONE: XXX
<selected zone descriptor>
►Z1 Z2 Z3 Z4 Z5
Z6 Z7 Z8 Z9 Z10
The user is first prompted to select the Zone number to be configured.
Press enter to continue.
ZONE <action type>
ACTIVATION MODE: EVACUATE
CHANGE
◄BACK NEXT►
The activation mode for each Zone action type can then be selected.
The activation mode choices are:
EVACUATE
ALERT
ALERT TIMEOUT EVACUATE
DELAYED
ZONE <action type>
ACTIVATION DELAY: 30 (0-999 SEC )
#CLEAR
◄BACK NEXT►
The activation mode screens are repeated for all action types in which the delays can be edited.
The user is then prompted to save any changes that may have been made.
7.6.5 Menu->Programming->Learn Options
LEARN OPTIONS MENU
1►AUTO LEARN 3|MISMATCHED DEVICES
2|EXTRA DEVICES 4|MISSING DEVICES
Auto Learn can be used to learn all Loops, Loop Devices, Panel Inputs and outputs
connected to the system and store the default configuration for all these points
Mismatched Devices is used to resolve any detected loop devices that do not match the
configuration
Extra Devices is used to learn any newly detected loop devices that do not exist in the
configuration
Missing Devices is used to remove any device that exist in the configuration but are
removed from physical connection to the loop
7.6.5.1 Menu->Programming->Learn Options->Auto Learn
Selecting Auto Learn firstly prompts for confirmation.