PV Cable Specifications

Description
ADC’s Solarlink brand Photovoltaic cable has a chemically cross-
linked polyethylene insulation with a sunlight resistant PVC jacket.
Applications
Appropriate for use in solar power applicatioins that require 600
volt rating. For use in grounded interconnection and unground
-
ed Photovoltaic power systems.
Construction
Conductors: Stranded bare copper conductor per ASTM B-3, B-8.
Available in 7 or 19 stranded versions as well as tinned copper.
Insulation: White Chemically Cross-linked polyethylene with
colored sunlight resistant PVC jacket.
Colors: Black, Green, White, Red. Print on one side with a con
-
trasting ink. An extruded stripe and other colors are available
upon request.
Industry Listings & Standards
UL Listed as Photovoltaic Cable per Standard Subject 4703 and 44
90°C Wet/105°C Dry Rated
Gasoline and Oil Resistant II
RoHS Compliant
Sunlight Resistant
VW-1 Rated
318DPV 18 7 45 30 .196 21.00 5.40
316DPV 16 7 45 30 .208 25.00 7.97
314DPV 14 7 45 30 .221 33.00 12.78
312DPV 12 7 45 30 .240 43.00 20.20
310DPV 10 7 45 30 .264 56.00 32.05
308DPV 8 7 60 30 .324 90.00 51.05
306DPV 6 7 60 30 .361 125.00 80.90
304DPV 4 7 60 30 .409 183.00 128.90
303DPV 3 7 60 30 .440 218.00 162.50
302DPV 2 7 60 30 .469 267.00 204.90
301DPV 1 19 80 30 .552 350.00 258.00
3010DPV 1/0 19 80 30 .593 428.00 326.00
3020DPV 2/0 19 80 30 .639 524.00 411.00
3030DPV 3/0 19 80 30 .690 644.00 518.00
3040DPV 4/0 19 80 30 .748 794.00 653.00
30250DPV 250 MCM 37 95 30 .825 948.00 772.00
30300DPV 300 MCM 37 95 30 .880 1,118.00 926.00
30350DPV 350 MCM 37 95 30 .931 1,289.00 1081.00
30400DPV 400 MCM 37 95 30 .978 1,458.00 1235.00
30500DPV 500 MCM 37 95 30 1.063 1,794.00 1544.00
30600DPV 600 MCM 61 110 30 1.173 2158.00 1853.00
30750DPV 750 MCM 61 110 30 1.278 2654.00 2309.00
P H O N E : ( 8 0 0 ) 3 4 3 2 5 7 9 F A X : ( 8 2 8 ) 3 8 9 3 9 2 2 W W W . A D C A B L E . C O M
PV PHOTOVOLTAIC CABLE
5
Dual Pass 600V Rated PV
Cross-Linked Polyethylene Insulated PVC Jacketed
18 - 750 MCM 600 Volts 105°C Dry and 90°C Wet
The information contained on this specification is intended to be used a guide in product selection and is believed to be reliable.
ADC has made every effort to ensure the data shown above is accurate at the time of publication. This specification is subject to change anytime without notice.
Cable Data
Part Number AWG Strand
Insulation
Thickness
(mils)
Jacket
Thickness
(mils)
Nominal O.D.
(inch)
Approximate
Net Weight
lbs/1M’
Copper Weight
per lbs/1M’
Cable Identification
18-16 AWG:ADVANCED DIGITAL CABLE INC. XX
AWG (UL) PV WIRE 600V 90C WET OR 105C DRY
SUN RES UV RATED VW-1
DIRECT BURIAL RoHS E324841”
14 AWG-750 MCM:ADVANCED DIGITAL CABLE
INC. XX AWG (UL) PV WIRE 600V 90C WET OR
105C DRY SUN RES UV RATED VW-1 OR RHW-2
DIRECT BURIAL RoHS E324841”
Bare Copper
XLPE Insulation
PVC Jacket