ACD-50NAV 600A AC Navigator Clamp ACD-51NAV 600A AC TRMS Navigator Clamp ACDC-52NAV 600A AC / DC TRMS Navigator Clamp ACD-53NAV 1000A AC TRMS Navigator Clamp ACDC-54NAV 1000A AC / DC TRMS Navigator Clamp Users Manual • • • • Mode d’emploi Bedienungshandbuch Manual d’Uso Manual de uso 1
ACD-50NAV 600A AC Navigator Clamp ACD-51NAV 600A AC TRMS Navigator Clamp ACDC-52NAV 600A AC/DC TRMS Navigator Clamp 1000A AC TRMS Navigator Clamp ACDC-54NAV 1000A AC/DC TRMS Navigator Clamp Users Manual December 2010, Rev.1 ©2010 Amprobe Test Tools. All rights reserved.
Limited Warranty and Limitation of Liability Your Amprobe product will be free from defects in material and workmanship for 1 year from the date of purchase. This warranty does not cover fuses, disposable batteries or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling. Resellers are not authorized to extend any other warranty on Amprobe’s behalf.
ACD-50 Series CAT IV Navigator Clamps Series 1 2 4 3 5 6 7 8 9 1 Jaw 2 Voltsense Light 3 Trigger 4 Hold / DCA Zero Key 5 Rotary Switch 6 Display 7 Navigator Key 8 V / e / E Input 9 Common Input
CONTENTS SYMBOLS......................................................................................................... 1 UNPACKING AND INSPECTION....................................................................... 2 FEATURES......................................................................................................... 2 OPERATION...................................................................................................... 3 Making Basic Measurement....................................
SYMBOLS X Caution ! Risk of electric shock � Caution ! Refer to the explanation in this Manual , Application around and removal from hazardous live conductors is permitted. T Equipment protected by double or reinforced insulation B Alternating Current (AC). F e G J Temperature Measurement E R Capacitance Measurement Continuity Beeper To alert you to the presence of a potentially hazardous voltage, when the Meter detects a voltage ≧30 V or a voltage overload (OL) in V. This symbol is displayed.
Measurement category: V : Category III 1000 Volts AC & DC, and Category IV 600 Volts AC & DC. A : Category III 1000 Volts AC & DC, and Category IV 600 Volts AC & DC. Per IEC 61010-1 2nd Ed. (2001) Measurement Category Measurement Category IV (CAT IV) is for measurements performed at the source of the low-voltage installation. Examples are electricity meters and measurements on primary overcurrent protection devices and ripple control units.
o DC Current - Up to 600A (ACDC-52NAV) - Up to 1000A (ACDC-54NAV) o Capacitance o Temperature Measurement in °C / °F (ACD-51NAV, ACDC-54NAV only) - Temp.
Auto Power Off After idle 15 min The meter can work again by turning it on from the OFF position. Auto Power Off (APO) disable : Press “Downward” of Navigator key while tuning meter on from OFF position. Navigator Key UP LEFT ENTER RIGHT DOWN The Navigator Key has 5 directions of switch on the display, toggle the navigator key to select the desired feature to activate the feature by a simple click.
Measuring Voltage V �WARNING To avoid electrical shock, hazard or damage to meter, do not attempt to measurement that might exceed 1000 V DC or AC RMS. Do not apply more than 1000 V DC or AC RMS to the input terminals. Note - If the measured voltage is higher than 30 V DC or AC RMS, the display will show “Y” symbol.
Measuring Current I �CAT IV 600V, CAT III 1000V with respect to earth for the jaw. Tactile Barrier for hand guard. �Do not hold the meter across the Tactile Barrier. I OK I I I OK OK I+(-I)=0 - Don’t clamp on any conductor while the meter power on. - ACD-50NAV, ACD-51NAV or ACD-53NAV has only AC current measurement mode. - Torch lighting when clamping. �CAUTION Please do not measure current from clamp jaw when temperature probe is connected to meter.
AUTO SENSE mode: Display measurement result at AC only with RMS value or DC value, it depends on whichever is greater. AC mode: AC only with RMS value. DC mode: DC value. AC+DC mode: AC+DC RMS value. Note: • Select “ AC”, “ DC” or “ AC+DC” indicator then press the navigator key to enter the AC/DC/AC+DC mode. • Select “ AC”,” DC” or “ AC+DC” indicator then press the navigator key for more than 2 seconds to return to the AUTO SENSE mode. PEAK HOLD (AC mode only) 1.
In PEAK HOLD mode, the meter is activated to save the positive peak value and negative peak value. Positive peak value is displayed in PEAK MAX mode. Negative peak value is displayed in PEAK MIN mode. Inrush Current : (AC mode only) If the under testing inrush current could be bigger than 100A ac, please select the range to 600A/1000A in advance before activating inrush current. ” indicator on the display to enter Inrush Current In ACA mode, select “ mode.
DC A ZERO (For ACDC-52NAV, ACDC-54NAV Only) Remove the jaw out of the conductor. Press HOLD Key > 2 seconds to compensate the residual magnetism. HOLD> 2 Sec HOLD - DC A Zero is only available in Auto Sense, DC and AC+DC mode. Measuring Frequency (AC mode only) Select the “Hz” indicator then press the navigator key to enter/exit the frequency measurement mode. "Hz" ENTER MAX/MIN/AVG Select the “MAX MIN” indicator then press the navigator key to enter the MAX/MIN/AVG mode.
"MAXMIN" "MAXMIN" ENTER MAXMIN >2sec "MAXMIN" "MAXMIN" Note : • Press HOLD key in MAX MIN mode to make the meter stop updating the maximum and minimum value. When the HOLD mode is activated in MAX MIN mode, the HOLD mode must be deactivated before the MAX MIN mode. THD Measurement (AC mode only) Select the “THD” indicator then press the navigator key to enter the THD mode. THD-F=RMS of Harmonics ÷ RMS of fundamental ×100%.
Individual Harmonic Measurement (AC mode only) Select the “ “ indicator then press the navigator key to enter the individual harmonic mode. To quit from the individual harmonic mode, press the navigator key for more than 2 seconds. Hn=RMS of Individual Harmonic ÷ RMS of fundamental ×100%.
Measuring Active Power (W) / Power factor (PF) 1. Single Phase Power Measurement Step1. Set the rotary switch to the “W” position. Step2. Connect the Red test lead to the Line conductor, and the Black test lead to the Neutral conductor. Step3. Press the trigger to open the transformer jaws and clamp one conductor only, make sure that the jaw is firmly closed around the conductor. Step4. Using the Navigator key to choose the “W/PF” mode.
2.Three Phase Power Measurement A. 3 phase 3 wire balanced / unbalanced Step 1. Set the rotary switch to the “W” position Step 2. Using the Navigator key to choose the “W” mode. W=W1+W2 1 3 2 Wye or star Red Red Black Black B. 3 phase 4 wire balanced / unbalanced Step1. Set the rotary switch to the “W” position Step2. Using the Navigator key to choose the “W” mode.
Phase Rotation Line 1 Line 2 Line 3 Note : • Connect three phase of power source as shown above. • The test is only available while the system frequency is stable. Step 1. Set the rotary switch to the “W” position. Step 2. Using the Navigator key to choose the “ “ mode Step 3. Connect the Red test lead and Black test lead to any of the line conductor (e.g. Red test lead to the phase Line 1, and Black test lead phase Line 3).
c) When displayed “- - - - “ means it is unable to determine line phases. d) If it displays “LoU”, it is possible that you remove the test leads before the meter completing its testing procedures. Step 5. To repeat the test, using the Navigator key and choose the “ “ mode again. OHM Measurement �CAUTION To avoid possible damage to the Meter or to the equipment under test, disconnect circuit power and discharge all high-voltage capacitors before measuring resistance and diode.
Measuring Capacitance Set the rotary switch to the “E“ position. Capacitance �CAUTION To avoid possible damage to the meter or to the equipment under test, disconnect circuit power and discharge all high-voltage capacitors before measuring capacitance. Use the DC voltage function to confirm that the capacitor is discharged. Note: The meter will display “diSC” while discharging the capacitor.
Measuring Temperature °C / °F ( For ACD-51NAV and ACDC-54NAV Only) Set the rotary switch to the “ ” position. ENTER "°F" Don’t take any high voltage measurement prior to accurate °C/°F measurements.
Measuring μA Current (For ACD-51NAV Only) Set the rotary switch to the μA position.
Other Function : AUTO/MANUAL Range Select the “RANGE“ indicator, then press the navigator key to enter the manual range mode. To return to the auto range mode, press the navigator key for more than 2 seconds. "Range" "ENTER" "Range" "Range" >2SEC HOLD Key Press HOLD key to freeze display value. Press Hold key SMART HOLD: The meter will beep continuously and the display will flash if the measured signal is larger than the display reading. (for V.A.
VoltSense The red diamond shape of LED will illuminate, if there has electric field been detected from the jaw. Buzzer The Meter beeps once for every valid key-press, and beeps twice for every invalid key-press. Power-up options Press one of the following keys while turning meter on from OFF position. Upward of Navigator key: Display of the software version. Downward of Navigator key: Disable auto power off. Leftward of Navigator key: Disable active backlight.
SPECIFICATIONS General Specifications Display count : 10000 or 4000 Measuring rate : 3 times / per second Overrange display : “OL” or “-OL” . Auto Power Off : Approx. 15 minutes. Low battery indicator : is displayed. Replace the battery when the indicator appears in the display. Power requirement : 9V battery. Battery life : ALKALINE 9V 50 hours (without Backlight). Environmental Conditions Indoor Use Calibration: One year calibration cycle.
Electrical Specifications Accuracy is ±(% reading + number of digits) at 23°C ± 5°C < 80%RH. (1) Voltage ACD-50NAV, ACD-51NAV, ACDC-52NAV, ACD-53NAV, ACDC-54NAV Function Range 99.99V DC V 999.9V AC V LPF Accuracy* ± (0.7% + 2dgt) 99.99V ± (1.0% + 5dgt) 999.9V 50 ~ 500Hz 99.99V 50 ~ 60Hz ± (1% + 5dgt) 999.9V 61 ~ 400Hz ± (5% + 5dgt) * DCV <1000dgt, add 6 dgt to the accuracy. ACV <1000dgt, add 3 dgt to the accuracy. Overload protection: 1000Vrms Input Impedance: 3.
ACDC-52NAV, ACDC-54NAV Function DC A Range 99.99A 599.9A / 999.9A* Accuracy ± (1.5% + 0.2A) ± (1.5% + 5dgt) ** 0.10A ~ 99.99A 50 ~ 60Hz ± (1.5% + 5dgt) ** 599.9A / 999.9A* 61 ~ 400Hz ± (2% + 5dgt) ** LPF 0.10A ~ 99.99A 50 ~ 60Hz ± (1.5% + 5dgt) ** AC A 599.9A / 999.9A* 61 ~ 400Hz ± (5% + 5dgt) ** AC A * ACDC-52NAV: 599.9A ; ACDC-54NAV: 999.9A ** The measured value <1000dgt, add 5 dgt to the accuracy.
(4) Frequency ACD-50NAV, ACD-51NAV, ACDC-52NAV, ACD-53NAV, ACDC-54NAV Function Range Accuracy 20.00 ~ 99.99Hz Frequency 20.0 ~ 999.9Hz ± (0.5% + 3dgt) 0.020 ~ 9.999KHz Overload protection : 1000 Vrms 600 Arms For ACD-50NAV, ACD-51NAV, ACDC-52NAV 1000 Arms For ACD-53NAV, ACDC-54NAV Sensitivity : 10~100Vrms for AC 100V range 10~100Arms for AC 100A range ( >400Hz Unspecified) 100~1000Vrms for AC 1000V range 100~600/1000Arms for AC 600A/1000A range ( >400Hz Unspecified) - Reading will be 0.
Overload protection: 1000 Vrms 600 Arms For ACD-50NAV, ACD-51NAV, ACDC-52NAV 1000 Arms For ACD-53NAV, ACDC-54NAV Accuracy defined for: Sine wave, ACA≧10Arms, Freq. 50/60Hz - Integration time about 100m seconds (7) Active Power : Watt (DC/AC) ACD-50NAV, ACD-51NAV, ACDC-52NAV, ACD-53NAV, ACDC-54NAV Function Range Accuracy 9.999KW** AC W / DC W A,error×V,reading+ 99.99KW 599.9KW / 999.9KW* V,error×A,reading * ACD-50NAV, ACD-51NAV, ACDC-52NAV: 599.9KW ACD-53NAV, ACDC-54NAV: 999.
(9) Resistance & Continuity & Diode: ACD-50NAV, ACD-51NAV, ACDC-52NAV, ACD-53NAV, ACDC-54NAV Function Range Resistance 9.999 ke 999.9 e 99.99 ke Accuracy ± (1.0% + 5dgt) ± (1.0% + 3dgt) Continuity 999.9 e ± (1.0% + 5dgt) Diode 0.40 ~ 0.80V ± (1.5% + 5dgt) Overload protection : 1000Vrms Max. Test Current : Approx. 0.5mA. Maximum Open Circuit Voltage for e, R Approx. 3V Maximum Open Circuit Voltage for diode : Approx. ±1.
(12) DC μA : ACD-51NAV Function Range Accuracy DCμA 999.9 μADC ± (1.7% + 2dgt)* *<1000dgt, add 3 dgt to the accuracy. Overload protection : 1000 Vrms MAINTENANCE AND REPAIR �CAUTION To avoid electrical shock, disconnect the meter from any circuit, remove the test leads from the input jacks and turn OFF the meter before opening the case. Do not operate with open case. Install only the same type of battery or equivalent Trouble Shooting If the instrument fails to operate, check battery, leads, etc.
�CAUTION Remove test leads from Meter before opening the battery cover or Meter case.