Versatile AC/DC Clamp-on Multimeter Series Users Manual ACDC100_Rev002 © 2010 Amprobe Test Tools. All rights reserved.
Limited Warranty and Limitation of Liability Your Amprobe product will be free from defects in material and workmanship for 1 year from the date of purchase. This warranty does not cover fuses, disposable batteries or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling. Resellers are not authorized to extend any other warranty on Amprobe’s behalf.
➊ Hall-effect Clamp Jaw for AC & DC current electric field pick up ➋ Hand/Finger Barrier to indicate the limits of safe access of the meter during measurement ➌ Push-buttons for special functions & features ➍ Input Jack for all functions EXCEPT noninvasive ACA & DCA current functions ➎ Common (Ground reference) Input Jack for all functions EXCEPT non-invasive ACA & DCA current functions ➏ Slide-switch Selector to turn the power ON/OFF and Select a function ➐ 3-3/4 digits 4000 counts LCD display
ACDC-100 TRMS / ACDC-100 Versatile AC/DC Clamp-on Multimeter Series Contents Symbols..............................................................................................................................................5 Safety Information............................................................................................................................5 Unpacking and Contents..................................................................................................................
Symbols � Battery � Refer to the manual � Double insulated � Dangerous Voltage � Direct Current � Earth Ground � Alternating Current � Audible tone � Conforms to relevant Australian standards. � Complies with EU directives � Do not dispose of this product as unsorted municipal waste. � Underwriters Laboratories. [Note: Canadian and US.
• Before and after hazardous voltage measurements, test the voltage function on a known source such as line voltage to determine proper meter functioning. • Keep your hands/fingers behind the hand/finger barriers (of the meter and the test leads) that indicate the limits of safe access of the hand-held part during measurement. • Inspect test leads, connectors, and probes for damaged insulation or exposed metal before using the instrument. If any defects are found, replace them immediately.
HOLD Press the HOLD button momentarily toggles to hold mode for all of the functions. To release the HOLD feature momentarily press the HOLD button. MAX Press the HOLD button for 1 second or more activates the MAX HOLD feature for the VDC, VAC and ACA functions. To release the MAX HOLD feature press the HOLD button for 1 second or more. r Relative Zero mode Relative Zero mode allows the user to offset the subsequent meter measurements with the displayed reading as the reference value.
AC Current (see Fig. 2) 1. Set the Function Switch to A� position. 2. Select AC current using the SELECT button. 3. Open spring-loaded clamp by pressing the lever on left side of meter. 4. Position clamp around one wire or conductor and release the clamp lever. Make sure that the clamp is entirely closed. The clamp must be positioned around only one conductor. If it is placed around two or more current carrying conductors, the reading is FALSE. 5.
3. Turn off power to the circuit being measured. 4. Free at least one end of the diode from the circuit. 5. Connect the test probes across the diode noting polarity. 6. Read the display. A good diode has a forward voltage drop of about 0.6 V. An open or reverse biased diode will read .0L. Capacitance (see Fig. 3) 1. Set the Function Switch to Ω and press the SELECT button until � is displayed. 2. Connect the test leads: Red to +, Black to COM. 3. Turn off power to the circuit being measured. 4.
Specifications General Specifications Display: 3-3/4 digits 4000 counts LCD display Update Rate: 3 per second nominal Polarity: Automatic Power Supply: standard 1.5V AAA Size (NEDA 24G or IEC R03) battery x Power Consumption: typical 11 mA for ACA/DCA and 2.9 mA for other functions APO Timing: idle for 30 minutes APO Consumption: typical 10µA for ACDC- 100 and 90µA for ACDC- 100 TRMS Low battery: below approx. 2.
Electrical (23 °C ± 5 °C) < 75% RH DC Voltage RANGE 400.0 mV 4.000V, 40.00V, 400.0V 600V Accuracy ± (0.3% + 3dgts) ± (0.5% + 3dgts) ± (1.0% + 4dgts) Resolution : 0.1 mV on 400 mV range NMRR : >50dB @ 50/60Hz CMRR : >20dB @ DC, 50/60Hz, Rs=1kΩ Input Impedance : 10MΩ, 30pF nominal (1000MΩ for 400.0mV range) Max input : 600VDC/VAC rms AC Voltage RANGE 400.0mV 1) 4.000V, 40.00V, 400.0V 4.000V, 40.00V, 400.0V 600V Resolution: 0.
Capacitance RANGE 1) Accuracy 2) 3) 500.0 nf, 5.000 µf, 50.00 µf, 500.0 µf, 3000 µf ± (3.5% + 6dgts) Resolution: 0.1 nf on 500.0 nf range 1) Additional 50.00nf range accuracy is not specified 2) Accuracies with film capacitor or better 3) Specified with battery voltage above 2.8V (approximately half full battery). Accuracy decreases gradually to 12% at low battery warning voltage of approximately 2.4V DC Current (Clamp-On) Accuracy 1) 2) RANGE 0.0A to 400.0A ± (1.5% + 4dgts) 400A to 800A ± (1.
Figure 1.
Figure 2.
Figure 3. — Resistance, Continuity, Capacitance and Diode functions Figure 4.