String Optimizer V1500-30 Series
Installation Manual: 57070016-1
v20201023
Failure to follow the prescribed connection and disconnection order can result
in damage to the device.
Follow these instructions to avoid damaging the device. Follow polarity
markings on the optimizer faceplate. Do not cross-wire inputs or output.
Use only MC4-Evo 2 mating connectors or connectors manufactured by
Stäubli that are recognized as being part of the MC connector family with the
appropriate rating.
Per Canadian Electrical Code, the installer is required to mark the device with
the following wording or equivalent, located on or adjacent to each wiring
compartment giving access to high voltage circuits, only if actually connected
to high voltage in the installation:
DANGER HIGH VOLTAGE
or
DANGER XXXX V
where XXXX is replaced by the rated voltage.
Connection/Disconnection Order Matters
The following label on the optimizer faceplate serves as a field reference to ensure proper
connection/disconnection order to avoid damaging the device. It is not meant to replace
the instructions that follow.
Figure 12: Connection order label on the optimizer faceplate
Connecting the Inputs
1. Read the warning, caution, and notice statements starting on page 20.
2. Make sure that the unit is properly mounted and grounded.
3. Make sure the strings of PV modules that will be connected to the inputs of the
optimizer meet the acceptable input criteria, fusing, and other requirements
outlined in Chapter 2.
4. For optimizer inputs with strings in parallel
a. Follow your safety procedures and protocols to prepare each set of PV
strings for each optimizer input.
i. Connect the PV modules in series for each string.
ii. Use an appropriately rated multimeter to verify the voltage and
polarity of each PV string before connecting in parallel.