Radiant Extrol Expansion Tanks Instruction Manual

READ CAREFULLY THE PRODUCT INSTALLATION,
OPERATING AND MAINTENANCE INSTRUCTIONS.
FAILURE TO FOLLOW THE INSTRUCTIONS AND WARNINGS IN THE
MANUAL MAY RESULT IN SERIOUS OR FATAL INJURY AND/OR
PROPERTY DAMAGE, AND WILL VOID THE PRODUCT WARRANTY.
THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED PROFESSIONAL.
FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND
REGULATIONS, IN THE ABSENCE OF SUCH CODES, FOLLOW THE
CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND
NATIONAL ELECTRIC CODE, AS APPLICABLE.
THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT
YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS.
OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO
REDUCE THE RISK OF POSSIBLE INJURY AS WELL AS
PROPERTY DAMAGE.
This Product, like most Products under pressure, may
over time corrode. weaken and burst or explode,
causing serious or fatal injury, leaking or flooding and/or property damage.
To minimize risk, a licensed professional must install and periodically inspect
and service the Product. A drip pan connected to an adequate drain must be
installed if leaking or flooding could cause property damage. Do not locate in
an area where leakage of the tank or connections could cause property
damage to the area adjacent to the appliance or to lower floors of
the structure.
EXPLOSION OR RUPTURE HAZARD. A relief valve
must be installed to prevent pressure in excess of local
code requirement or maximum working pressure designated in the Product
Manual, whichever is less. Do not expose Product to freezing temperatures
or temperatures in excess of 200° F. Do not adjust the pre-charge or
re-charge this Product except for any adjustments at the time of the initial
installation, especially if Product is corroded,damaged or with diminished
integrity. Adjustments to pre-charge must be done at ambient temperature
only. Failure to properly size the Product or follow these instructions may
result in excessive strain on the system and may lead to Product
failure,serious or fatal personal injury, leakage, and/or property damage.
Note: Inspect for shipping damage and notify freight carrier or store where
purchased immediately if damage is present. To avoid risk of personal injury
and property damage, if the product appears to be malfunctioning or shows
signs of corrosion, call a qualified professional immediately. Current copies
of the Product manual can be viewed at www.amtrol.com. Use proper safety
equipment when installing.
FAILURE TO PROPERLY SEAL WILL RESULT IN
LOSS OF PRECHARGE CAUSING PRODUCT
TO FAIL.
POTABLE WATER WARNING. Radiant Extrol
®
must
not be used in potable water systems of any kind. The
maximum operating pressures in these systems exceeds the maximum safe
working pressure of the Product. Use Therm-X-Trol
®
for potable
water applications.
CALIFORNIA PROPOSITION 65 WARNING! This
product contains a chemical known by the State of
California to cause cancer and to cause birth defects or other reproductive
harm. (California Installer/Contractor - California law requires that this notice
be given to consumer/end user of this product.) For more information: www.
amtrol.com/prop65/htm.
Pre-Installation
1. Visually inspect RADIANT EXTROL
®
for any damage.
2. Adjust pre-charge to equal system fill pressure.
3. Replace and tighten plastic cap on air fitting.
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY
Boiler
Boiler
Return
Boiler
Supply
AMTROL
®
Air Purger
and Float Vent
Zone
Circulator(s)
In-Line Models
RX-15 & RX-30
RADIANT
EXTROL
Boiler
Boiler
Return
Boiler
Supply
AMTROL
®
Air Purger
and Float Vent
Zone
Circulator(s)
Stand Models
RX-60 and larger
RADIANT
EXTROL
Figure 1.
MARK OF THE ORIGINATOR
Installation
1. Drain the boiler system or isolate the area where the RADIANT
EXTROL
®
will be installed.
2. Install the RADIANT EXTROL
®
on the supply side of the boiler, on the
suction-side of the zone circulator(s) (see Figure 1).
3. Once the RADIANT EXTROL
®
is installed, re-pressurize the system
and check for leaks. Repair as necessary.
4. Restart the boiler system and check for relief valve discharge. If the
relief valve drips, the tank may be improperly charged or undersized.
5. The RADIANT EXTROL
®
is now operational and will absorb expanded
water during boiler operation.
Maintenance
1. A heating system professional should check the complete heating system,
including the RADIANT EXTROL
®
, yearly and more frequently as the
system ages.
Operation
1. The RADIANT EXTROL
®
is installed on the supply-side of the boiler
system. Its sealed-in air pre-charge prevents water from entering the
tank until the system pressure begins to rise.
2. As the water temperature rises, water enters the RADIANT
EXTROL
®
.
3. As the system cools, the diaphragm is forced downward. Water is
expelled from the RADIANT EXTROL
®
, back into the heating system.
NOTES:
Although the RADIANT EXTROL
®
does not have to be installed at the base of an
air purger, this installation is recommended to reduce air in the system and provide
a compact installation. Some method of air elimination is required to ensure an
oxygen-free system.
* Models RX-15 through RX-60 come with a 5 year warranty. All other
RADIANT EXTROL
®
models come with a 1 year warranty. See reverse side
for warranty information.
1400 Division Road, West Warwick, RI 02893 T: 401.884.6300 F: 401.885.2567 www.amtrol.com
INSTALLATION & OPERATION INSTRUCTIONS
RADIANT EXTROL
®
Radiant Heating System Expansion Tanks
Part #: 9015-367 (02/11)